5
Startup with EtherNet/IP™
Controlling the stations in test run
Manual – MOVI‑C
®
CONTROLLER standard UHX25A
56
5.5
Controlling the stations in test run
During successful communication between PLC and the MOVI‑C
®
CONTROLLER,
process data words are transferred between the devices without faults.
5.5.1
Transferring process data words to the MOVI-C
®
CONTROLLER
The process data exchange is monitored and controlled in Logix Designer with "Con-
troller Tags".
Proceed as follows:
ü
You loaded the MOVISUITE
®
project to the MOVI‑C
®
CONTROLLER via the
IEC Editor.
ü
The connection between the PLC and the MOVI‑C
®
CONTROLLER is set up (the
PLC is in RUN mode).
1. Switch to the Logix Designer project.
2. In the "Controller Organizer", select the "Controller Tags" area.
ð
The right-hand screen pane displays the process data words that the PLC ex-
changes with the MOVI‑C
®
CONTROLLER.
24519820043
ð
In this example, these process output data words are sent to the
MOVI‑C
®
CONTROLLER.
25800736/EN – 08/2018