5
Startup with EtherNet/IP™
Configuration of the fieldbus stations
Manual – MOVI‑C
®
CONTROLLER standard UHX25A
47
6. Select the number of process data words that you wish to use for communicating
with the subordinated slaves. Set the data format for the process data words. The
process data always contain 16 bits (data format INT).
24518069131
ð
In this example, the IP address of the MOVI‑C
®
CONTROLLER is:
192.168.10.40. 16 process data words are assigned to each application in-
verter module (slave of the MOVI‑C
®
CONTROLLER) for communication. This
makes a total of 3 x 16 = 48 process data words.
7. If the direct integration of the device description file is not supported, set the follow-
ing connection parameters:
Assembly instance
Value
PO Data Exclusive Owner
120
PI Data Exclusive Owner
130
Listen Only
192
Input Only
193
8. Save the Logix Designer project.
25800736/EN – 08/2018