5
Startup with EtherNet/IP™
Configuration of the EtherCAT®/SBusPLUS stations
Manual – MOVI‑C
®
CONTROLLER standard UHX25A
35
5.3
Configuration of the EtherCAT
®
/SBus
PLUS
stations
Configurati
on of the
EtherCAT®/
SBusPLUS
stations
In the project example, the following devices are EtherCAT
®
/SBus
PLUS
stations:
•
The MOVI-C
®
CONTROLLER serves as EtherCAT
®
/SBus
PLUS
master.
•
The application inverters serve as EtherCAT
®
/SBus
PLUS
slaves.
The configuration of the devices is performed in the MOVISUITE
®
engineering soft-
ware.
The EtherCAT
®
/SBus
PLUS
stations are configured in several process steps:
2. "Scanning the network for devices" (→
5.3.1
Establishing a connection between engineering PC and MOVI-C
®
CONTROLLER
To ensure that the engineering PC can communicate via the engineering interface
X80 with the MOVI‑C
®
CONTROLLER via Ethernet, both the devices must be connec-
ted in the same local network. For this purpose, the IP address parameters of the en-
gineering PC must be set to the local network.
INFORMATION
In delivery state, the engineering interface X80 of the MOVI-C
®
CONTROLLER has
the following IP address parameters: Standard IP address 192.168.10.4, subnet
mask 255.255.255.0
Proceed as follows:
1. Select the network settings in the Windows control panel.
2. Double-click on the adapter that is physically connected to the engineering inter-
face X80 of the MOVI‑C
®
CONTROLLER.
25800736/EN – 08/2018