![SEW-Eurodrive DFE32B PROFINET IO Manual Download Page 76](http://html1.mh-extra.com/html/sew-eurodrive/dfe32b-profinet-io/dfe32b-profinet-io_manual_1250328076.webp)
76
Manual – DFE32B Fieldbus Interface PROFINET IO
7
Structure of the PROFINET parameter channel
Parameterization via PROFIdrive Data Set 47
7.2.3
Addressing connected inverters
The structure of the DS47 data set defines an
axis
element. This element is used to
reach multi-axis drives that are operated via one PROFINET interface. The
axis
element
addresses one of the units connected via the PROFINET interface.
Addressing a
MOVIDRIVE
®
B
on the PROFINET
With the setting
Axis = 0
, the parameters of the MOVIDRIVE
®
B drive inverter are ac-
cessed. Since there are no drive units connected to the MOVIDRIVE
®
B, an access with
Axis > 0
is returned with an error code.
62210AXX
Read / Write
Record
Axis = 0
Cyclic OUT Data
Cyclic IN Data
PD
PD
PROFINET
PROFINET
Controller
0
0
I
Summary of Contents for DFE32B PROFINET IO
Page 2: ...SEW EURODRIVE Driving the world...
Page 131: ......