Manual – DFE32B Fieldbus Interface PROFINET IO
55
6
Process data configuration
Operating Behavior in Conjunction with PROFINET
6.3
Process data configuration
For the DFE32B option, Slot 1 must be set to "slot not used". Slot 2 allows for modules
with 1 to 10 I/O words. After the unit has been switched on and before the IO controller
establishes the communication, the configuration is set to 3 process data words I/O. It
can be changed by the IO controller while the communication is being established. The
current configuration is displayed in
P090 PD configuration
.
Permitted config-
urations
The DAP (Device Access Point) is designated as ID 100 (slot 0, subslot 1)
ID
Process data length
101
1 I/O process data word
102
2 I/O process data words
103
3 I/O process data words
104
4 I/O process data words
105
5 I/O process data words
106
6 I/O process data words
107
7 I/O process data words
108
8 I/O process data words
109
9 I/O process data words
110
10 I/O process data words
INFORMATION
The project planning for the DFE32B option is compatible to the DFE12B option. That
means that you do not have to change the project planning when you replace the
DFE12B option with the DFE32B option. The DFE32B option then accepts 1 ... 10 pro-
cess data words 10 process data words.