Manual – DFE32B Fieldbus Interface PROFINET IO
31
5
Project planning for the PROFINET IO controller
Project Planning with PROFINET
•
INFORMATION
: For the following step, the IO controller must not yet be in a cyclic
data transmission with the IO devices.
Specify an IP address [5] and a subnet mask [4] as well as a router address [7] if re-
quired. Click the [Assign IP configuration] [3] button.
• Click the [Browse] [6] button again to check whether your settings have been adopt-
ed.
Click [Close] [1].
• Click [Reset] [9] to reset the device name of the DFE32B online. Now you need to
restart the DFE32B.
5.1.2
Project planning for the PROFINET interface for MOVIDRIVE
®
B
Creating a new
project
Start the SIMATIC Manager and create a new project. Select your control type and add
the required modules. The OB82, OB86 and OB122 modules are particularly useful.
The OB82 module makes sure that the controller does not go to "STOP" for so-called
diagnostic alarms. The OB86 module indicates the failure of the decentralized periph-
ery. The OB122 module is called up if the controller cannot access data of a node of the
decentralized periphery. This can occur, for example, when the DFE32B is ready for op-
eration later than the control system.
• Start STEP7 HWCONFIG and select the PN-IO slot in the control rack.
• Add a PROFINET IO system by right-clicking the context menu with your mouse.
Specify an IP address for the PROFINET IO controller when doing this. Add a new
PROFINET subsystem using the [Ethernet] button.
• in the hardware catalog, open [PROFINET IO] / [Additional Field Devices] / [Drives]
/ [SEW] / [DFE/DFS(2Ports)] [1].
There are several entries.
68064AEN
[1]
[2]