When unit has been tested, the compressor Enabled property will be
changed to No.
When Commissioned option still is set to No, unit will start up in service
mode. It is not possible to start the unit in Normal Mode. The blower can
be started anytime but to enable the compressors and to be able to change
the Commissioned option, a factory password is required.
When changing Commissioned to Yes, all the logs will be cleared and the
unit will do a system restart. Now at startup you will see the normal
startup screen with 2 selections, Normal Mode and Service Mode.
The Commissioned option can be changed back to No if needed.