Seresco CommandCenter Manual Download Page 2

Enter key has a special meaning. From any menu screen it will take you directly back 
to the main screen (the sensor screen). If you now press the Back key it will take you 
back to the screen where you were before pressing Enter. On the sensor screen you 
can still use the Up and Down arrows to scroll up and down a page and the Back key 
will still take you back to where you were before pressing Enter. If you press 1 
however (Main Menu) the back shortcut is lost (it’s not a true history list yet).

Key 3 on the sensor screen is another hidden feature. It will toggle sensor readings 
between displaying values with a one decimal prevision and no precision. Default is 
no precision. This applies to all temperatures and the humidity level.

To enter Edit mode you select the number key corresponding to the data item you want to 
edit on a navigation screen with data items. To indicate that you are in edit mode, the data 
value is highlighted.

The following keys are used in Edit mode:

Keys 1-3 are not used.

Up and Down arrows are used to scroll up and down in the value list. More info 
about different types of data items later in this document.

Back key takes you back to navigation mode and cancel any changed data. Data is 
with other words not saved when you press the Back key.

Enter key will save the data and most of the time take you directly back to 
navigation mode (covered under data types).

Data Types

Most of the data (properties) you can change are changed using values in a selection list. 
You use the Up and Down arrows to scroll up and down in the selection list. You can 
scroll “around the corner”. For data items with only two selection items (e.g. Yes/No), 
you can use either the up or down key to toggle between the two values.

Most Integer values are edited as lists with a min and max range. The value might also be 
restricted to be changed in specific increments (e.g. 5, 10, 15, 20, …).  In a few rare cases 
integer values are entered one digit a time. When entering edit mode, the integer value 
will be displayed as a five digit zero padded number. To enter a number less than 5 digits, 
leave the first digits at 0. Press Enter until all digits are set.

Date and Time values are edited in a special way. Using date as an example, when 
entering edit mode, the year (or last two digits of the year) will be highlighted. Use Up 
and Down arrows to change year. When done, press Enter. Now the month will be 
highlighted and you change it in the same way. Press Enter again and the day is 
highlighted. Pressing Enter a final time will save the new date. Pressing Back at any time 
when editing the date will cancel the change operation and take you back to navigation 
mode.

OperatorPanel_4.15.14.doc

Page 2

7/12/2012

Summary of Contents for CommandCenter

Page 1: ...l start otherwise blower will remain off and there will be a voltage monitor fault alarm Navigation Mode and Edit Mode The menu system implements two different modes where the keys have different mean...

Page 2: ...hen you press the Back key Enter key will save the data and most of the time take you directly back to navigation mode covered under data types Data Types Most of the data properties you can change ar...

Page 3: ...essages will popup over current menu screen The message can be cleared by pressing either key 1 or 2 Key 1 will clear current message and key 2 will clear all queued messages Messages can be of three...

Page 4: ...s displayed in the summary 1 Setpoints 1 1 Temperature 1 2 Humidity 1 3 Pool Temp Optional 1 4 Economizer Optional 1 5 Freeze Stat Optional 1 6 Purge Temp Optional 1 7 Heat Recovery 2 Schedule 2 1 Emp...

Page 5: ...ote OP Only visible on Remote OP 4 4 1 Version Info 4 4 2 RS 232 Port 4 4 3 RS 485 Port 5 Factory Settings 5 1 System 5 1 1 Role 5 1 2 Fire Reset 5 1 3 Temp Unit 5 1 4 Rem Control 5 1 5 Rem Cntrl 2 5...

Page 6: ...ting 5 3 2 13 Learning 5 3 2 14 Emergency Heat 5 3 3 Humidity 5 3 3 1 Deg Min On 5 3 3 2 Deg Min Off 5 3 3 3 Temp Offset 5 3 3 4 High Humidity 5 3 3 5 Float Setpoint 5 3 4 Pool Heating 5 3 4 1 Enabled...

Page 7: ...5 4 12 Alarm Stop 5 4 13 Anti Block 5 4 14 Wakeup Mode 5 4 15 Wakeup Time 5 4 16 SucTempL Dly 5 4 17 SucTempH Dly 5 4 18 DisTempL Dly 5 4 19 LP Alarm 5 4 20 LP Start 5 4 21 LP Max 5 4 22 HP Min 5 4 23...

Page 8: ...o Test 5 5 2 3 Port D RS 485 5 5 2 3 1 User 5 5 2 3 2 Baud Rate 5 5 2 3 3 Databits 5 5 2 3 4 Parity 5 5 2 3 5 Echo Test 5 5 3 WebSentry 5 5 3 1 Enabled 5 5 3 2 Use DNS 5 5 3 3 IP 5 5 3 4 Port 5 5 3 5...

Page 9: ...1 16 Discharge 2 5 6 1 17 Exhaust Air 5 6 1 18 Reheat Temp 5 6 1 19 Pool 2 In 5 6 1 20 Pool 2 Out 5 6 2 Sensor Type 5 6 2 1 Rel Humidity 5 6 2 2 Return Air 5 6 2 3 Outdoor Air 5 6 2 4 HP 1 5 6 2 5 LP...

Page 10: ...Damper 6 2 2 3 Open Damper 6 2 2 4 Close Damper 6 2 2 5 Exhaust Fan 1 6 2 2 6 Exhaust Fan 2 6 2 2 7 OACC 6 2 3 Heating 6 2 3 1 Heater 1 6 2 3 2 Heater 2 6 2 3 3 Mod Heat 6 2 3 4 Pool 1 Heater 6 2 3 5...

Page 11: ...6 4 Clear Alarm Log 6 5 Clear All Logs 6 6 Commission 6 6 1 Tested 6 6 2 Commissioned OperatorPanel_4 15 14 doc Page 11 7 12 2012...

Page 12: ...ault does not apply e g Weekends Sunday 3 System 3 1 Ventilation Currently you can only turn the blower on or off on this screen Note that the blower might not come when turning it on There can be an...

Page 13: ...s The status screen shows the status for different internal system components It s main purpose is for troubleshooting a running system where the information here can be passed back to tech support Th...

Page 14: ...settings are Time zone can be set to 3 30 4 00 to 10 00 and GMT time The daylight property only determines if an extra hour should be added to the current time No automatic detection if we need to add...

Page 15: ...vice password 5 1 System The Role property is used in units with more than 2 compressor circuits or when two units control the same space One unit or master board is configured as Master while second...

Page 16: ...verload alarm BP Damper 50 sets the time it takes to open the bypass damper halfway starting from fully closed BP Damp Stable timer is the amount of time the bypass damper will wait after it has adjus...

Page 17: ...t Delay to control for how long a heating issue condition need to last before heating control will be reset and start all over again Use Reset Time to control for how long the heating control will be...

Page 18: ...ity setpoint based on the outdoor air temperature as follows More than 50 F 50 Between 30 F and 50 F 45 Between 10 F and 30 F 40 Less than 10 F 35 There is a 2 degree deadband when moving to a higher...

Page 19: ...d to configure setpoint deadbands Air temperature and pool temperature setpoints can be set in 1 10th of a degree 5 3 6 Sensors Outdoor Air property control whether the outdoor air sensor should be us...

Page 20: ...e is not closing properly Using this timer will close both solenoid valves when one valves needs to be closed After timeout the other valve is opened Typically you will not set this one to more than 3...

Page 21: ...gh suction temperature alarm DisTempL Dly is the debounce delay timer for the low discharge temperature alarm LP Alarm pressure setting controls at what Low Pressure level compressor will trip on Low...

Page 22: ...seconds means valve will open for 5 seconds and then be closed for 55 seconds Valve Open timer determines for how long valve will be open in a full valve cycle see Valve Cycle 5 5 Network 5 5 1 TCP IP...

Page 23: ...e the port even with the hardware error Reply Delay defines for how long we will wait for a reply message before considering it a communication fault 5 5 3 WebSentry These properties controls WebSentr...

Page 24: ...o set a unique device ID for unit on the BACnet network Port can be used to change the default port setting 5 5 5 Modbus Use these properties to configure Modbus communication 5 5 6 LON Use these prop...

Page 25: ...ts are read and translated into alarms or other inputs A digital input will signal a state change when all samples are the same and are different from current saved state 6 Service To reach these sett...

Page 26: ...to monitor by using the arrows keys Select 1 to start monitoring To stop pause messages you can press key 2 anytime Press Enter to clear the screen Select back top stop console or to go back and selec...

Page 27: ...tarted anytime but to enable the compressors and to be able to change the Commissioned option a factory password is required When changing Commissioned to Yes all the logs will be cleared and the unit...

Reviews: