Seresco CommandCenter Manual Download Page 24

Comm Segment

 is how often the system will try to connect to the 

WebSentry server between disconnects when we can not transmit 
all non-sent data in one session.

Stay Alive

 is how long the TCP connection will stay active from 

the last time a message was received from the WebSentry server. 
Normally the WebSentry server should disconnect before this time.

5.5.4.BACnet

These properties controls BACnet connections and are only 
available if the CommandCenter has been loaded with BACnet 
support.

Set 

Enabled

 to Yes to enabled BACnet. It is disabled by default.

Set 

Interface

 to BACnet interface type. Currently only Ehernet 

and IP is supported.

Use 

Device ID

 to set a unique device ID for unit on the BACnet 

network.

Port

 can be used to change the default port setting.

5.5.5.Modbus

Use these properties to configure Modbus communication.

5.5.6.LON

Use these properties to configure LON-Modbus gateway 
communication.

5.6. IO Configuration

5.6.1.Sensor Calibration

All sensor calibration values are changed the same way. You use
the up and down arrow to change the value to a few steps above or
below 0.

5.6.2.Sensor Type

The sensor types controls how an input signal is translated into a 
value. Note that some sensors that are available under sensor 
calibration are not available under sensor types. These are 
temperature sensors that never should be disabled and for which 
there are no other sensor type that can be used except Thrm.

The following sensor types are available:

OperatorPanel_4.15.14.doc

Page 24

7/12/2012

Summary of Contents for CommandCenter

Page 1: ...l start otherwise blower will remain off and there will be a voltage monitor fault alarm Navigation Mode and Edit Mode The menu system implements two different modes where the keys have different mean...

Page 2: ...hen you press the Back key Enter key will save the data and most of the time take you directly back to navigation mode covered under data types Data Types Most of the data properties you can change ar...

Page 3: ...essages will popup over current menu screen The message can be cleared by pressing either key 1 or 2 Key 1 will clear current message and key 2 will clear all queued messages Messages can be of three...

Page 4: ...s displayed in the summary 1 Setpoints 1 1 Temperature 1 2 Humidity 1 3 Pool Temp Optional 1 4 Economizer Optional 1 5 Freeze Stat Optional 1 6 Purge Temp Optional 1 7 Heat Recovery 2 Schedule 2 1 Emp...

Page 5: ...ote OP Only visible on Remote OP 4 4 1 Version Info 4 4 2 RS 232 Port 4 4 3 RS 485 Port 5 Factory Settings 5 1 System 5 1 1 Role 5 1 2 Fire Reset 5 1 3 Temp Unit 5 1 4 Rem Control 5 1 5 Rem Cntrl 2 5...

Page 6: ...ting 5 3 2 13 Learning 5 3 2 14 Emergency Heat 5 3 3 Humidity 5 3 3 1 Deg Min On 5 3 3 2 Deg Min Off 5 3 3 3 Temp Offset 5 3 3 4 High Humidity 5 3 3 5 Float Setpoint 5 3 4 Pool Heating 5 3 4 1 Enabled...

Page 7: ...5 4 12 Alarm Stop 5 4 13 Anti Block 5 4 14 Wakeup Mode 5 4 15 Wakeup Time 5 4 16 SucTempL Dly 5 4 17 SucTempH Dly 5 4 18 DisTempL Dly 5 4 19 LP Alarm 5 4 20 LP Start 5 4 21 LP Max 5 4 22 HP Min 5 4 23...

Page 8: ...o Test 5 5 2 3 Port D RS 485 5 5 2 3 1 User 5 5 2 3 2 Baud Rate 5 5 2 3 3 Databits 5 5 2 3 4 Parity 5 5 2 3 5 Echo Test 5 5 3 WebSentry 5 5 3 1 Enabled 5 5 3 2 Use DNS 5 5 3 3 IP 5 5 3 4 Port 5 5 3 5...

Page 9: ...1 16 Discharge 2 5 6 1 17 Exhaust Air 5 6 1 18 Reheat Temp 5 6 1 19 Pool 2 In 5 6 1 20 Pool 2 Out 5 6 2 Sensor Type 5 6 2 1 Rel Humidity 5 6 2 2 Return Air 5 6 2 3 Outdoor Air 5 6 2 4 HP 1 5 6 2 5 LP...

Page 10: ...Damper 6 2 2 3 Open Damper 6 2 2 4 Close Damper 6 2 2 5 Exhaust Fan 1 6 2 2 6 Exhaust Fan 2 6 2 2 7 OACC 6 2 3 Heating 6 2 3 1 Heater 1 6 2 3 2 Heater 2 6 2 3 3 Mod Heat 6 2 3 4 Pool 1 Heater 6 2 3 5...

Page 11: ...6 4 Clear Alarm Log 6 5 Clear All Logs 6 6 Commission 6 6 1 Tested 6 6 2 Commissioned OperatorPanel_4 15 14 doc Page 11 7 12 2012...

Page 12: ...ault does not apply e g Weekends Sunday 3 System 3 1 Ventilation Currently you can only turn the blower on or off on this screen Note that the blower might not come when turning it on There can be an...

Page 13: ...s The status screen shows the status for different internal system components It s main purpose is for troubleshooting a running system where the information here can be passed back to tech support Th...

Page 14: ...settings are Time zone can be set to 3 30 4 00 to 10 00 and GMT time The daylight property only determines if an extra hour should be added to the current time No automatic detection if we need to add...

Page 15: ...vice password 5 1 System The Role property is used in units with more than 2 compressor circuits or when two units control the same space One unit or master board is configured as Master while second...

Page 16: ...verload alarm BP Damper 50 sets the time it takes to open the bypass damper halfway starting from fully closed BP Damp Stable timer is the amount of time the bypass damper will wait after it has adjus...

Page 17: ...t Delay to control for how long a heating issue condition need to last before heating control will be reset and start all over again Use Reset Time to control for how long the heating control will be...

Page 18: ...ity setpoint based on the outdoor air temperature as follows More than 50 F 50 Between 30 F and 50 F 45 Between 10 F and 30 F 40 Less than 10 F 35 There is a 2 degree deadband when moving to a higher...

Page 19: ...d to configure setpoint deadbands Air temperature and pool temperature setpoints can be set in 1 10th of a degree 5 3 6 Sensors Outdoor Air property control whether the outdoor air sensor should be us...

Page 20: ...e is not closing properly Using this timer will close both solenoid valves when one valves needs to be closed After timeout the other valve is opened Typically you will not set this one to more than 3...

Page 21: ...gh suction temperature alarm DisTempL Dly is the debounce delay timer for the low discharge temperature alarm LP Alarm pressure setting controls at what Low Pressure level compressor will trip on Low...

Page 22: ...seconds means valve will open for 5 seconds and then be closed for 55 seconds Valve Open timer determines for how long valve will be open in a full valve cycle see Valve Cycle 5 5 Network 5 5 1 TCP IP...

Page 23: ...e the port even with the hardware error Reply Delay defines for how long we will wait for a reply message before considering it a communication fault 5 5 3 WebSentry These properties controls WebSentr...

Page 24: ...o set a unique device ID for unit on the BACnet network Port can be used to change the default port setting 5 5 5 Modbus Use these properties to configure Modbus communication 5 5 6 LON Use these prop...

Page 25: ...ts are read and translated into alarms or other inputs A digital input will signal a state change when all samples are the same and are different from current saved state 6 Service To reach these sett...

Page 26: ...to monitor by using the arrows keys Select 1 to start monitoring To stop pause messages you can press key 2 anytime Press Enter to clear the screen Select back top stop console or to go back and selec...

Page 27: ...tarted anytime but to enable the compressors and to be able to change the Commissioned option a factory password is required When changing Commissioned to Yes all the logs will be cleared and the unit...

Reviews: