5.3.3.Humidity
The
Deg*Min On/Deg*Min Off
properties controls for how long
the control logic will wait until adding or removing a
Dehumidification stage after a stage has been added/removed.
Temp Offset
property is the offset from the return air temperature
where dehumidification will not operate. If temperature is outside
this range, dehumidification ill not come on even the humidity is
above the high deadband. However, if dehumidification already is
running, the will keep on running even if the temperature moves
outside the range.
High Humidity
property is the offset above setpoint at which
dehumidification will start no matter what the return air
temperature is.
Float Setpoint
property is used to enable/disable the floating
humidity setpoint feature. This feature dynamically sets the
humidity setpoint based on the outdoor air temperature as follows:
More than 50 F
50%
Between 30 F and 50 F
45%
Between 10 F and 30 F
40%
Less than 10 F
35%
There is a 2 degree deadband when moving to a higher setpoint so
that moving from 40% to 45% will not happen until outdoor air
reaches 32 F.
5.3.4.Pool Heating
Set
Enabled
property to Yes to enable pool heating.
Set the
2 Pools
property to Yes to enable heating of a second pool
using compressor circuit 2. Set to Bypass to support pool bypass
valves on older units.
Comp Heat
property controls how compressor pool heating valve
and auxiliary pool heater is being utilized. For
Normal
setting, unit
will use both heating resources in the most efficient way.
Forced
will force compressor on to heat pool even when there is no other
compressor demand. Auxiliary heater will not be used for this
setting. For
Disabled
setting compressor pool heating is disabled
and only auxiliary heater will be used to heat the pool.