The
Deg*Min On/Deg*Min Off
properties controls for how long
the control logic will wait until adding or removing a Heating stage
after a stage has been added/removed.
Modulated Step
defines the increments for the modulated signal
when heater is configured as a modulated heater.
Stage 2 On
controls when the second stage digital output will be
turned on for a modulated heater. First stage is turned on when
heating is started.
Heat Off
controls the off point for a modulated heater (0 or 10
volts).
Use
Reset Offset
to set number of degrees below setpoint at which
the unit will consider there is a heating problem (heater not
working).
Use
Reset Delay
to control for how long a heating issue condition
need to last before heating control will be reset and start all over
again.
Use
Reset Time
to control for how long the heating control will be
in reset mode before starting to heat again.
Cold Start
determines under what temperature we consider being
in cold conditions at startup of unit.
Use
Cold Level
to set the startup heating level when starting up in
cold conditions.
Save Heating
determines for how long last heating level will be
saved when a unit is restarted or shutdown.
Use the
Learning
option to disable the learning feature and just
use deadbands as turning on/off points.
Enabling
Emergency Heat
will disable normal auxiliary heating
control. Instead the compressor will be started to provide heat if
the space gets too cold.