IMD Drive installation guide
R1724
- 27 -
SERAD S.A
2-11-
Connecting a motor brake
The output Q2 is NPN open collector, 100mA max. The load must be
connected between Q2 and +24Vdc.
Using the iDPL parameter set-up window, select the function Brake for output 2.
It is obligatory to put the 2 protection diodes else drive components can be
damaged.
2-12-
System checks before starting
With the Enable input off, switch on the auxiliary 24V dc supply.
Ensure that on the
STATUS display,
the point blinking.
Apply power.
If the Status display shows an
error message
check the list of error codes.
X7
READY
24DC
100mA
Statique
Relay
8
7
6
5
4
3
2
1
i1
i2
i3
i4
DGND
Q1
Q2
F2
Brake
Motor
24Vcc
+
-
0v
+24Vcc
External
Power
24Vcc
+/- 10%
F1
diode
protect
DRIVE
IMD
protect
diode
+24Vcc
Input