ENGLISH
Pag. 59
Or in case just Fault/Emergency situation is present:
Figure 28) Active events screen with fault only
In case of a new event, the screen will automatically switch to the Active Events list and the
buzzer will sound. The user cannot go back to the main screen until the event is acknowled-
ged. In figure 25 the shown events are not yet acknowledged. When acknowledged there is
a “X” under the column “A” of the related event (see fig. 26 and 27).
In this screen there are four available options:
1 ACK
2 RESET
3 CHANNEL
4 PRINT
ACK
By pressing 1-ACK with the cursor on the active event, this will get acknowledged. There are
two situations:
1. The user is already logged in. In this case by pressing 1-ACK the screen image will
simply refresh and an “X” mark will appear on the “A” column (the “Acknowledged” co-
lumn). The control panel buzzer will stop ringing.
2. The user is not yet logged in. In this case the LOGIN dialogue window pops up and
the user should insert in the password. After which the “X” mark will be shown under
the “A” column of the related active event. The control panel buzzer will stop ringing.
Practically this is the only situation when the login of an “Operator” level user is requi-
red in order to keep track of the person who acknowledged the active event.
RESET
By pressing 2-RESET with the cursor on the active event previously acknowledged (the one
marked with “X”), this will get reset and the event will disappear from the active events list.
As described above, there are two situations:
1. The user is already logged in for a previous operation that requires login. In this case
pressing 2-RESET the screen image will simply refresh and delete the event line from
the list