TECHNICAL SPECIFICATIONS 

 
 

TECHNICAL SPECIFICATIONS 

 

Analogue/digital converter 

24 Bit > of 16777000 points 

Type of measurement 

Unipolar  ratiometric  (compression  only)  or  bipolar  ratiometric 
(compression and traction) 

Noise digital filter 

New  advanced  digital  filter  with  configurable  response  time 
from 16ms to about 2s.  
Filter advanced configuration possibility. 

Analogue output response time 

About 5ms. 

Modbus port (RS485) response time 

About 6ms. 

Net weight resolution 

Configurable, factory-set on 10000 points (automatic). 

Isolated analogue output resolution 

10000 points 

Operating mode 

Calibration  with  sample  weight  (in  the  field)  or  without 
calibration (factory calibration). 

Isolated digital input/output 

Yes, configurable between input/output. 

USB port 

Yes,  on  the  front  for  the  configuration,  calibration,  register 
reading. 
Drivers  Virtual  com  port  for  Windows  ™,  Linux,  MAC  OS, 
Windows CE 

Configuration and calibration software 

Easy Setup, free. For Windows operating systems. 

Isolated digital input functions 

Configurable between tare reset or external digital input. 

Isolated digital output functions 

Configurable in alarm mode: 
- Cell bottom scale exceeded 
- Threshold and stable weighing exceeded 
- Stable weighing 
- Generic output controlled by Modbus 
- Threshold exceeded with hysteresis 

Isolated analogue output (only Z-SG2) 

Voltage/Current configurable. 
Fully configurable on the 0-10V / 0-20mA range.  

Firmware update 

Yes for the addition of new functions. 

Sensitivity 

From +-1 mV/V to +-64 mV/V 

“Stable weighing” function 

Yes, configurable 

Automatic tare tracker function 

Yes, configurable 

Piece counting function 

Yes, configurable 

“Manual tare” function 

Yes,  configurable.  It  does  not  need  to  acquire  the  tare  value 
from the field but it can be entered manually. 

Summary of Contents for Z-SG2

Page 1: ...GINAL INSTRUCTIONS USER MANUAL Z SG2 Z SG2 L DIGITAL LOAD CELL CONVERTER WITH 24 BIT ADC SENECA S r l Via Austria 26 35127 Z I PADOVA PD ITALY Tel 39 049 8705355 8705355 Fax 39 049 8706287 www seneca...

Page 2: ...ible for failures breakages and accidents caused by ignorance or failure to apply the stated requirements Seneca is not responsible for any unauthorized modifications Seneca reserves the right to modi...

Page 3: ...S 13 DIGITAL OUTPUT INPUT CONNECTIONS 14 ANALOGUE OUTPUT CONNECTIONS Z SG ONLY 14 RS485 PORT CONNECTIONS 15 CONFIGURATION OF THE RS485 PORT BY DIP SWITCH 17 CONFIGURATION OF THE FLASH MEMORY RS485 POR...

Page 4: ...LL SCALE 25 10 2 13 2 EXCEEDING THE THRESHOLD AND STABLE WEIGHING 25 10 2 13 3 STABLE WEIGHING 26 10 2 13 4 MODBUS CONTROLLABLE 26 10 2 13 5 EXCEEDED THRESHOLD WITH HYSTERESIS ALARM 26 STABLE WEIGHING...

Page 5: ...IBRATION WITH MANUALLY INSERTED TARE 35 CALIBRATION PROCEDURE WITH AN EXTERNAL DEVICE CALIBRATION WITH SAMPLE WEIGHT 35 MODBUS RTU SLAVE COMMUNICATION PROTOCOL 36 SUPPORTED MODBUS FUNCTION CODES 36 MO...

Page 6: ...hat the functions fully meet the customer s expectations or that the device firmware and software should have no errors or operate continuously DESCRIPTION Z SG2 is a load cell converter strain gauge...

Page 7: ...tal input output Yes configurable between input output USB port Yes on the front for the configuration calibration register reading Drivers Virtual com port for Windows Linux MAC OS Windows CE Configu...

Page 8: ...0 to 115200 bit s configurable Parity Delay in replying Configurable USB RS485 port protocol Modbus RTU Slave LED SIGNALS Z SG2 Z SG2 L LED LED SIGNALS ON THE Z SG2 Z SG2 L FRONT LED STATUS LED MEANIN...

Page 9: ...immunity requirements use shielded signal cables connect the shield to a preferential instrumentation earth system separate shielded cables from other cables used for power installations transformers...

Page 10: ...y 10 40 C Since the cable resistance depends on the temperature the response of the cable to temperature changes must be eliminated The 4 wire cable is part of the load cell temperature compensation s...

Page 11: ...cell has 6 wires check that the same voltage is also measured between Sense and Sense Now leave the cell at rest without the tare and check that the voltage between the Signal and Signal cables is ar...

Page 12: ...N PARALLEL IMPEDANCE OF THE STATED LOAD CELL Ohm MAXIMUM NUMBER OF CONNECTABLE CELLS IN PARALLEL 350 4 1000 8 For the connection of 4 load cells Seneca recommends using the SG EQ4 product To connect 2...

Page 13: ...y 20 potentiometer is inserted in the Excitation cable of each load cell There are two ways to trim the load cells The first method is to adjust the potentiometers by trial shifting the calibration we...

Page 14: ...he mV V value of the other load cells 5 Measure and adjust the excitation voltage of the other three load cells using the respective potentiometer Check the results and make a final adjustment by movi...

Page 15: ...IOR PERMISSION www seneca it Doc MI 005370 EN Rev 1 0 0 2 Page 15 Analogue current output RS485 PORT CONNECTIONS The device has an RS485 serial port to be connected to the Z PC DINAL accessory and the...

Page 16: ...Z SG2 L ALL RIGHTS RESERVED NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION www seneca it Doc MI 005370 EN Rev 1 0 0 2 Page 16 The protocol available through the RS485 port is...

Page 17: ...ion address of the RS485 port ATTENTION The configuration via dip switch is active only after a restart ATTENTION The configuration via dip switch has priority over the one saved in flash if you need...

Page 18: ...0 2 Page 18 SETTING THE BAUD RATE OF THE RS485 PORT BY DIP SWITCH Dip switches 1 and 2 configure the baud rate Baud Rate DIP1 DIP2 9600 OFF OFF 19200 OFF ON 38400 ON OFF 57600 ON ON ATTENTION The par...

Page 19: ...ry convention Modbus Station Address DIP3 DIP4 DIP5 DIP6 DIP7 DIP8 1 OFF OFF OFF OFF OFF ON 2 OFF OFF OFF OFF ON OFF 3 OFF OFF OFF OFF ON ON 4 OFF OFF OFF ON OFF OFF 5 OFF OFF OFF ON OFF ON 6 OFF OFF...

Page 20: ...is necessary to install the free Easy Setup software suite which can be downloaded in section Z SG2 Z SG2 L of the www seneca it website EASY SETUP MENU Connect Allows connecting the device to the PC...

Page 21: ...the dip switch settings OPERATING MODE It allows to configure the basic operation of the device can be set to factory calibration or to Calibration with Sample weight 10 2 1 1 FACTORY CALIBRATION It...

Page 22: ...pression the measurement will have the sign if traction it will have the sign A typical case of use is to link the direction of the force to the analogue output so that for example 4mA correspond to t...

Page 23: ...ters to be used only by experts or on the advice of Seneca personnel ADVANCED FILTERING These parameters can only be configured by expert personnel or at the suggestion of Seneca 10 2 9 1 NUMBER OF SA...

Page 24: ...R RESPONSE SPEED It represents a parameter related to the filter response speed it can vary from 0 001 slowest response to 1 fastest response NET WEIGHING RESOLUTION It is the resolution with which th...

Page 25: ...channel is configured as an input or an output DIGITAL INPUT CONFIGURATION If the digital channel is set as an input it is possible to select its behaviour 10 2 12 1 ACQUIRES THE TARE In this mode if...

Page 26: ...an be controlled directly by modbus see STATUS register in the chapter 16 6 10 2 13 5 EXCEEDED THRESHOLD WITH HYSTERESIS ALARM In this mode the output is activated when the net weight reaches the thre...

Page 27: ...ght set value NET WEIGHING ALARM It is the threshold value in technical units see 10 2 13 HYSTERESIS It is the hysteresis value used in the digital output mode EXCEEDED THRESHOLD WITH HYSTERESIS see 1...

Page 28: ...selects the baud rate to be used in the communication from the RS485 port PARITY It sets whether the communication of the RS485 port must take place with or without even or odd parity DELAY IN REPLYI...

Page 29: ...ON OF THE MEASUREMENTS It allows to configure the type of representation of the floating point values of the measurements while the configuration parameters do not change operation 10 2 25 1 FIRST PAR...

Page 30: ...Microsoft Excel The sample acquisition time can be set minimum 1 second The data logger will create a text file in a standard csv format CALIBRATION OF THE LOAD CELL WITH THE EASY SETUP SOFTWARE In t...

Page 31: ...ELD In the tare acquisition mode from the field proceed as follows for calibration 1 Replace the tare on the cell 2 Wait for the measurement to stabilize 3 Press the TARE ACQUISITION FLASH button FACT...

Page 32: ...libration 1 Set the Tare value in technical units 2 Press the SET MANUAL TARE FLASH button ATTENTION To obtain better measurement accuracy use the tare acquisition mode from the field CELL CALIBRATION...

Page 33: ...cell 2 Wait for the measurement to stabilize 3 Press the TARE ACQUISITION FLASH button 4 Replace the Tare Sample Weight 5 Wait for the measurement to stabilize 6 Press the SAMPLE WEIGHT ACQUISITION F...

Page 34: ...e downloaded from the device s web page The drivers are however installed automatically with the installation of the Easy Setup software DRIVERS FOR LINUX SYSTEMS In many Linux distributions the drive...

Page 35: ...ment the calibration of a load cell by sending Modbus commands depending on the type of operation chosen CALIBRATION PROCEDURE WITH AN EXTERNAL DEVICE FACTORY CALIBRATION WITH TARE ACQUIRED FROM THE F...

Page 36: ...MMAND REGISTER 9 The device saves the new sample weight value in flash and resets the COMMAND REGISTER value 10 The load cell is calibrated MODBUS RTU SLAVE COMMUNICATION PROTOCOL The communication pr...

Page 37: ...User Manual Z SG2 Z SG2 L ALL RIGHTS RESERVED NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION www seneca it Doc MI 005370 EN Rev 1 0 0 2 Page 37...

Page 38: ...read only RW Read write register RW Reading and writing register contained in flash memory writable a maximum of 10000 times Unsigned 16 bit unsigned integer register can take values from 0 to 65535...

Page 39: ...RESS OFFSET NUMBERING OF MODBUS ADDRESSES WITH 1 BASED CONVENTION STANDARD The numbering is that established by the Modbus consortium and is of the type HOLDING REGISTER MODBUS ADDRESS 4x MEANING 4000...

Page 40: ...T 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1 0 0 MSB and LSB BYTE CONVENTION WITHIN A MODBUS HOLDING REGISTER A Modbus Holding Register consists of 16 bits with the following convention BIT 15 BIT 14 BIT 13 BIT 12...

Page 41: ...swap the most significant word with the least significant word therefore it is possible to obtain 40064 as LSW and 40065 as MSW TYPE OF 32 BIT FLOATING POINT DATA IEEE 754 The IEEE 754 standard https...

Page 42: ...16 BIT 40002 1 FIRMWARE REVISION FIRMWARE REVISION RO UNSIGNED 16 BIT 40003 2 UNIT UNIPOLAR MSB UNIT Selects the unit of measurement among 0 Kg 1 g 2 t 3 lb 4 l 5 N 6 bar 7 atm 8 Other LSB UNIPOLAR 0...

Page 43: ...onse in number of characters RW UNSIGNED 16 BIT 40006 5 OUTPUT STOP SCALE V mA Full scale value of the analogue output in V mA MSW RW FLOATING POINT 32 BIT 40007 6 Full scale value of the analogue out...

Page 44: ...IT 40030 29 Ratio value of the load cell sensitivity in mV V MSW RW 40031 30 CELL FULL SCALE kg g t Full scale value of the load cell in technical units MSW RW FLOATING POINT 32 BIT 40032 31 Full scal...

Page 45: ...EIGHT kg g t Value of the delta weight in technical units for the stable weighing condition MSW RW FLOATING POINT 32 BIT 40042 41 Value of the delta weight in technical units for the stable weighing c...

Page 46: ...advanced is set RW UNSIGNED 16 BIT 40047 46 ADVANCED ADC CHOPPING Enables or disables the ADC Chopping mode For further information please refer to 10 2 9 2 It is active only if level 7 filtering adva...

Page 47: ...7 filtering advanced is set MSW RW FLOATING POINT 32 BIT 40052 51 Represents the variation in ADC points due to noise alone It is active only if level 7 filtering advanced is set LSW RW 40053 52 ADVA...

Page 48: ...d filter level FILTER LEVEL RESPONSE TIME ms 0 16 1 32 2 50 3 250 4 400 default 5 900 6 1800 7 ADVANCED Dependent on the configuration The higher the filter level the more stable but slow the weight m...

Page 49: ...lution calculated based on full scale to get 10000 points DENOISE FILTER ENABLE LSB 0 Noise filter disabled advanced mode 1 Noise filter enabled RW UNSIGNED 16 BIT 40057 56 MANUAL RESOLUTION kg g t Se...

Page 50: ...to 65535 In the case of bipolar measurement It can vary from 0 max traction to 32767 min traction From 32768 condition of 0 or rest to 65535 max compression RO UNSIGNED 16 40063 62 RESERVED RO UNSIGN...

Page 51: ...EGER GROSS WEIGHT kg g t Value of the gross weight in technical units MSW RO SIGNED 32 BIT 40073 72 Value of the gross weight in technical units LSW RO 40074 73 INTEGER TARE WEIGHT kg g t Value of the...

Page 52: ...ld Stable weighing BIT 1 RO Bit 1 1 The cell has reached full scale BIT 2 RO Bit 2 1 Net weight is 0 BIT 3 RO Reserved BIT 4 RO Bit 4 1 Weighing is stable BIT 5 R W Only if the modbus controlled outpu...

Page 53: ...the tare in RAM on restart it is lost 49914 decimal Acquires the tare in Flash for the calibration procedure in both operating modes factory calibration and with sample weight 50700 decimal Acquires...

Page 54: ...nits from restart LSW RO 40084 83 MIN NET WEIGHT kg g t Minimum value of the net weight in technical units from restart MSW RO FLOATING POINT 32 BIT 40085 84 Minimum value of the net weight in technic...