SETTING THE MODBUS STATION ADDRESS OF THE RS485 PORT BY DIP SWITCH
Dip switches 3 to 8 are used to configure the modbus station address of the RS485 port using the binary
convention:
Modbus
Station
Address
DIP3
DIP4
DIP5
DIP6
DIP7
DIP8
1
OFF
OFF
OFF
OFF
OFF
ON
2
OFF
OFF
OFF
OFF
ON
OFF
3
OFF
OFF
OFF
OFF
ON
ON
4
OFF
OFF
OFF
ON
OFF
OFF
5
OFF
OFF
OFF
ON
OFF
ON
6
OFF
OFF
OFF
ON
ON
OFF
7
OFF
OFF
OFF
ON
ON
ON
8
OFF
OFF
ON
OFF
OFF
OFF
9
OFF
OFF
ON
OFF
OFF
ON
10
OFF
OFF
ON
OFF
ON
OFF
11
OFF
OFF
ON
OFF
ON
ON
12
OFF
OFF
ON
ON
OFF
OFF
13
OFF
OFF
ON
ON
OFF
ON
14
OFF
OFF
ON
ON
ON
OFF
15
OFF
OFF
ON
ON
ON
ON
…
…
…
…
…
…
…
63
ON
ON
ON
ON
ON
ON
ATTENTION !
To set station addresses > 63 it is necessary to use the Easy Setup software.