User Manual
Z-SG2 / Z-SG2-L
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
www.seneca.it
Doc: MI-005370-EN
Rev. 1.0.0.2
Page 50
ADDRESS
(4x)
ADDRESS
OFFSET
REGISTER
DESCRIPTION
W/R
TYPE
40061
60
FLOATING POINT
ORDER
Selects whether the RO
registers in floating point
format are displayed in the
modbus registers in H/L or
L/H:
0 = Displays the registers in
H/L
1 = Displays the registers in
L/H
RW**
UNSIGNED
16 BIT
40062
61
16 BIT ADC
FILTERED
16-bit filtered and scaled ADC
value
In the case of unipolar
measurement it can vary from
0 to 65535
In the case of bipolar
measurement
It can vary from 0 (max
traction) to 32767 (min
traction)
From 32768 (condition of 0 or
rest) to 65535 (max
compression)
RO
UNSIGNED
16
40063
62
RESERVED
-
RO
UNSIGNED
16
40064
63
NET WEIGHT
[kg/g/t…]
Value of the net weight in
technical units (MSW*)
RO
FLOATING
POINT 32
BIT
40065
64
Value of the net weight in
technical units (LSW)
RO
40066
65
GROSS WEIGHT
[kg/g/t…]
Value of the gross weight in
technical units (MSW*)
RO
FLOATING
POINT 32
BIT
40067
66
Value of the gross weight in
technical units (LSW*)
RO
40068
67
TARE WEIGHT
[kg/g/t…]
Value of the tare in technical
units (MSW*)
RO
FLOATING
POINT 32
BIT
40069
68
Value of the tare in technical
units (LSW*)
RO
40070
69
INTEGER NET
WEIGHT
Value of the net weight in
technical units (MSW)
RO
SIGNED 32
BIT