USER MANUAL – S203TA-D / S203RC-D
46
Energy ratio
reactive energy.
to set Varh write 1
to set KVarh write 1000
to set MVarh write 1000000
etc…
bits
(KVarh)
40049(LS)
Cfg flags
Control
flags
bitwise.
(0 = LSB)
Bit
0
=
energy
values
protection from reset through
RS485 (1 for enabled).
Bit 1 = if set to 1, the digital
output energy sign values
reactive energy instead of
active energy.
Unsigned
16 bits
RW 0
40050
Demand Time
Time (minutes) on which the
average
active
power
is
evaluated
(0
=
function
disabled)
Unsigned
16 bits
RW 15
40051
Cut off
current
Minimum
current
(mA)
necessary to activate the
energy counter.
Unsigned
16 bits
RW 50
40052
Command
Command register.
To reset the device, write
0xDEAD
To set a positive energy
value for phase A, write the
value
(in integer unsigned
32 bits format)
in Command
aux
1
(high
part)
and
command aux 2 (low part),
then
write
0xBACA
in
Command register
To set a positive energy
value for phase B, write the
value
(in integer unsigned
32 bits format)
in Command
aux
1
(high
part)
and
command aux 2 (low part),
then
write
0xBACB
in
Command register
To set a positive energy
value for phase C, write the
value
(in integer unsigned
32 bits format)
in Command
aux
1
(high
part)
and
command aux 2 (low part),
then
write
0xBACC
in
Command register
To set a negative energy
value for phase A, write the
value
(in integer unsigned
32 bits format, the firmware
add itself the sign)
in
Command aux 1 (high part)
and command aux 2 (low
Unsigned
16 bits
RW 0
40131