USER MANUAL – S203TA-D / S203RC-D
45
Measure
linked To
analog output
0=VRMS, 1=IRMS, 2=Active
power, 3=Cosfi
Unsigned
16 bits
RW 2
40030
Start Scale
OUTPUT
Start scale value for output in
use.
Float
32
bits
RW 4.0 mA
40031(MS)
40032(LS)
End Scale
OUTPUT
End scale value for output in
use.
Float
32
bits
RW 20.0 mA
40033(MS)
40034(LS)
Digital output
energy ratio
0.0
= the digital output it’s
in
“Energy
sign
configuration
”
Other values:
Digital output make a pulse
when
energy
has
an
increment of a given value of
energy E. Default value is
1.0. Measure unit of the
energy value is Wh (or Varh),
KWh (or KVarh), MWh (or
MVarh), depending on the
selected measure unit of
“Energy ratio” register.
Float
32
bits
RW 1.0
40035(MS)
40036(LS)
Active Energy
ratio
Configure measure unit of
energy.
to set Wh write 1
to set KWh write 1000
to set MWh write 1000000
etc…
Float
32
bits
RW 1000.0
(KWh)
40037(MS)
40038(LS)
Command
aux 1
See Command register
-
W
0
40039
Command
aux 2
See Command register
-
W
0
40040
TV ratio
Voltage
transformer
ratio
value
Float
32
bits
RW 1.0
40041(MS)
40042(LS)
Phase linked
to digital
output
Selected phase to switch the
digital
output
(if
digout
function
is
“energy sign
configuration”)
0=phase A,
1=phase B,
2=phase C,
3=three phase
Unsigned
16 bits
RW 3
40043
Model Type
0 = S203TA-D
1 = S203RC-D (Input suitable
for a +-50mV rogowski coil
full scale)
2 = S203RC-D (Input
suitable
for
a
+-100mV
rogowski coil full scale)
3 = S203RC-D (Input suitable
for a +-200mV rogowski coil
full scale)
Unsigned
16 bits
RW 0 for S203TA-D
2 for S203RC-D
40044
Digital Output
Logic
Select the logic for digital
output switching.
0 = Normally open
1 = Normally close
Unsigned
16 bits
RW 0
40047
Reactive
Configure measure unit of Float
32 RW 1000.0
40048(MS)