USER MANUAL – S203TA-D / S203RC-D
33
6.3.1.
C) Out Measure
PARAMETER
VALUES
C1) OUTPUT PHASE
Phase to link to the analog output:
3-phase = ABC measure value
Phase A = phase A measure
Phase B = phase B measure
Phase C = phase C measure
Default: 3-phase
C2) OUT MEASURE
Measure to link to the analog output:
VRMS = Vrms linked to the analog output
IRMS = Irms linked to the analog output
PACT= Active Power linked to the analog output
COSFI= Power factor linked to the analog output
Default: PACT
C3) IN STARTSCALE
Start Scale Measure linked to the output
With this measure value the output will be at 0%
Default: 0.0 W
C4) IN ENDSCALE
End Scale Measure linked to the output
With this measure value the output will be at 100%
Default: 9000.0 W
C5) OUTPUT TYPE
Analog output type:
mA = Output in current mode
V = Output in voltage mode
Default: mA