A conditional expression only takes the form of a single expression with AND,
OR, NOT.
Eg. AND operation of Input #1 and Input #2
: I1 & I2
OR operation of Output #3 and Input #1
: O3 | I1
AND operation of the inversed Input #10 and Output #10
: !I10 & O10
Inverse operation of Input #1
: !I1
-
The number of points that can be specified for run condition per 1 output point in
setting data must be less than 21 points.
Eg. I1&I2&I3|I4|!I5|I6&I7&I8&I9&I10|!I11|I12|
O2|O3|O4|O5|O6|O7|O8|O9|O10
-
An output port to be set should not be included in run condition.
Eg. When setting O1, it should not be included in its run condition expression.
2)
Set Delay/Pulse.
-
It specifies the output to toggle between ON/OFF at a given time or repeatedly.
(Delay ON and Pulse are enabled with ON control command and disabled with
OFF control. Delay OFF is enabled with OFF control.)
-
Setting Data
Setting Data (time)
ON Time
OFF Time
Byte Size
5
5
Run Setting
“00000”-“50000”
“00000”-“50000”
A setting can be specified in 100 ms and allowed up to 500 sec.
Eg.
ON Time
OFF Time
Remark
“00000”
“00000”
No Delay/Pulse
“00001”
“00000”
ON after 100 ms delay
“00020”
“00000”
ON after 2 sec delay
“50000”
“00000”
ON after 5,000 sec delay
“00000”
“00001”
OFF after 100 ms delay
“00000”
“00020”
OFF after 2 sec delay