TB MRD1-T 10.01 E
33
5.3.3
Transformer ratings
Key
D
isplay
Parameter
A
vailable
in
MRD1
-
T2 T3
Select
Setting range
(
•
no selection)
Default
a
ctual
Set 1
S
et 2
S
et 3
S
et 4
Headline
××
none
••
•
•
•
•
rated apparent power of
winding 1(High-voltage-side)
××
10 kVA - 800 MVA
17.3 MVA
corresponding to winding 2
×
10 kVA - 800 MVA
17.3 MVA
corresponding to winding 3
×
10 kVA - 800 MVA
17.3 MVA
rated voltage of winding 1
(phase to phase voltage on high-
voltage-side)
××
100 V....800 kV
20 kVA
corresponding to winding 2
××
100 V....800 kV
6.6 kV
corresponding to winding 3
×
100 V....800 kV
6.6 kV
rated primary current of phase CT
winding 1
××
1.....50.000 A
500 A
corresponding to winding 2
××
1.....50.000 A
1500 A
corresponding to winding 3
×
1.....50.000 A
1500 A