TB MRD1-T 10.01 E
5.1.4
LEDs
LEDs arranged at the relay front can light up in dif-
ferent colours and can also either show permanent
light or flash in different frequencies.
LED lights up
ON / OFF-ratio
green / red
ein / on
aus / off
green / red flashing a
green / red flashing b
t
Meaning of the LED-signals
LED name
LED lights up
Meaning
POWER
green
•
Device OK
red flashing a
•
FAULT of an internal supply
off
•
Device OFF
TRIP
off
•
Normal
red
•
Trip
red flashing a
•
Energized
TEST
off
•
Normal
red flashing a
•
OFFLINE-TEST-mode active
EDIT
off
•
Normal, VIEW mode
red
•
EDIT mode after password access
MODIFIED
off
•
Normal
red
•
EDIT mode: parameter modified
Relay
off
•
Relays off
red
green
•
Relays energized
•
Relay-test
red flashing b
•
Relay off after energizing (until DEVICE RESET)
red flashing a
•
Relay blocked
SELFTEST
green
•
Protection o.k. (selftest relay on)
red
•
System initialization (after power on)
red flashing a
•
OFFLINE TEST mode / Relay-TEST. no protec-
tion, only messages
off
•
Internal fault. no protection