32
TB MRD1-T 10.01 E
5.3.2
Overview
Key
Pages
Headline
Parameter
see
leaf to next
page
or
Parameter pages active parameter ready for viewing
(e.g. set 1)
selected set ready for viewing and editing
(e.g. set 2)
Data of pro-
tected device for
all windings
W 1
W 2
W 3
Rated power
Rated voltage
CT primary current
Connection group
Phase shift
tap ratio
CT connection
5.3.3
parameter of
differential-
protection
Difference current at Is=0
×
In
Difference current at Is=2
×
In
Difference current at Is=10
×
In
max. Difference current Idiff>>
d[Id] Offset in case of harmonics
5.3.4
Parameter of lo-
gic functions
Assignment of protective and logic functions
(AND-logic)
Parameter of
output relays
Reset time or self-holding of the output relay
5.3.5
Parameter of ex-
ternal blocking
Table: Parameter pages, overview
On the first attempt to change a setting with the
+/- keys in a edit session the password is asked. To
view only parameter settings the PARA key is used to
leaf to the next page and the UP/DOWN keys are
used to select the parameter.