50
TB MRD1-T 10.01 E
5.5.2
Overview
Key
Test
Description
execute
scroll
Headline
Display of version and date of the software
only
display
Test
Test of the LEDs:
all LEDs will be illuminated green and red for two
seconds (no password needed)
Test
Test of the output relays:
IMPORTANT: all relays will be energised in a 1 s
interval. The Selftest Relay keeps off for the duration
of the test. After the test all relays will be set to the
state before.
"
Test
Memory / program test:
This routine will test the memory and the program
by calculating a checksum.
"
NOTE: Password is needed, because the protection function is disabled during the test!
Table: Implemented test routines