SecuriLan network units and MIC711
Mounting and installation, Technical Description, T 811 086 en e
87 / 128
9.3
B6-LAN interface unit
The B6-LAN is for non-redundant networking of PC applications with SecuriFire 2000 or for non-redundant networking of Se-
curiFire participants. It has one Ethernet network interface.
The unit is fitted on the expansion slot of the B6-BCB13.
Further information about the B6-LAN can be found in the technical description T 811 123.
9.3.1
Interfaces
X1
B6-BCB13 connector plug (rear side)
X2
LAN Ethernet interface (RJ-45 connector)
PIN assignment (X2)
Fig. 108 B6-LAN interfaces
PIN
X2
Ethernet signal
1
TX+
2
TX-
3
RX+
4
Termination
5
Termination
6
RX-
7
Termination
8
Termination
9.3.2
Technical data
Unit
Power supply:
via SecuriFire 2000 main control unit
Power consumption:
<1 mA
Ambient temperature:
0°C to +50°C
LAN interfaces 10/100
10/100
Connection:
Ethernet 100BASE-TX
Transmission type:
TCP/IP
Direction:
bidirectional, full-duplex operation
Speed:
max. 100 Mbit/s
Coverage:
max. 100 m
Mechanical design:
RJ-45 connector, 8-pin
9.3.3
Compatibility information
Compatible main control unit:
SecuriFire 2000 B6-BCB13
SecuriFire-Studio:
from release 1.1