SecuriFire 1000/2000 control panels
18 / 128
Mounting and installation, Technical Description, T 811 086 en e
2.3
B6-ADB 10 additional box
Fig. 2 B6-ADB 10
Empty B6-ADB10 housing for integrating the SecuriLine eXtended modules, remote
alerting devices, two 12 V/18 Ah emergency power accumulators or other devices.
2.4
B6-MIC11 built-in control panel
Fig. 3 B6-MIC11
The B6-MIC11 is language neutral and is located in the door of the Securi-
Fire 1000/2000 map case B6-SCP1020, B6-SCP1030, B6-SCP2020, B6-SCP2030,
B6-SCP2040 and B6-SCP2050. It is connected to the main control unit with a ribbon
cable and also controls the protocol printer.
2.5
Mounting a control panel
Fig. 4 Drilling plan for all SecuriFire 1000/2000 map case
variants (all dimensions in mm)
Mount rear wall according to drill plan with 4 pcs. 5 x 40
round screws and 4 pcs. S 8 dowels. When mounting
on plaster board, appropriate dowels and reinforcement
may be necessary. Weight including batteries: approx.
20 kg.
Insert cable and use cable fastener for strain relief.
Place batteries and connect.
Wire mains connection and plug of the units.
Mount map case and fix in place with two screws.
Connect the ribbon cable of the indication and control
map to the main control unit.
Connect earth cable of the door to the map case.
Notice
Rating plates
Each SecuriFire 1000/2000 map case is delivered with two rating plates. One of them is attached at the factory
on the right inside in the map case over the batteries. The second rating plate is packaged with the control
panel and has to be attached before commissioning in access level 1 (outside on the map case) where it can be
easily seen.