EPI-BUS devices
Mounting and installation, Technical Description, T 811 086 en e
83 / 128
8.10
B5-EPI-FPD fire brigade control panel
Via the
Extended Bus
(EPI-BUS) by means of a patch cable and an
8-pin RJ45 plug, the fire brigade control panel can be connected to
any SecuriFire MIC11 / MIC711 as well as to the B5-MMI-FIP and
B5-MMI-IPS devices.
Additional EPI devices can be connected to the second RJ45.
Via the hex coding switch you can set one of the three possible
EPI-BUS addresses. For each MMI-BUS participant with an EPI-
BUS interface, up to three EPI devices can be connected.
More information about the B5-EPI-FPD can be found in the Tech-
nical Description T 811 077.
Fig. 105 B5-EPI-FPD
8.10.1
Interfaces
EPI P
ort A “INCOMING”
EPI Port B “OUTGOING”
Designation
Terminal
Terminal
Designation
GNDP
1
2
VP
3
4
EXTBUS-
+3V3
5
6
+3V3
GNE
7
8
GND
8.10.2
Technical data
Operating voltage:
3,3 V
Quiescent current:
6 mA
Data transmission:
Electrical:
EPI-BUS
RS485
Distance to the MIC main indication and control map: max. 1 m
Protection class:
IP 30
Ambient temperature:
-5 °C to +50 °C
Dimensions:
Dimensions without map case:
185 x 255 x 65 mm (W x H x D)
Map case colour:
grey RAL 7032
8.10.3
Compatibility information
SecuriFire Studio
from release 1.2
EPI-Interface
B5-MIC (all versions), B6-MIC (all versions)
B5-MMI-FIP, B5-MMI-IPS
Notice
From which side the EPI bus “INCOMING” or
“OUTGOING” is connected is not relevant.
For purposes of clarity, however, we recommend
continuing with one connection system once be-
gun.