Expansion units for SecuriFire 2000
Mounting and installation, Technical Description, T 811 086 en e
41 / 128
Jumper setting
The operating mode of the inputs can be set using jumpers X11 to X20. At the same time the corresponding operating mode
has to be planned with software (SecuriFire Studio).
The following applies to all jumpers from X11 to X20:
VDS
X
..
HX
Jumper HX
connected
Detection zones
SecuriStar 521 / 563
MCP collective
MMD130 Ex-i
HX 130, HX 130 Ex-i
Fig. 50 Jumper setting
VDS
X
..
HX
Jumper VDS
connected
Monitored input 3k
VdS extinguishing input
Valve monitoring
Hochiki Ex-i detector
SLR-E-IS, DCD-1E-IS
VDS
X
..
HX
Jumper open
Monitored input 26k7
Connection assignment for plug (X2)
Connection assignment for plug (X3)
Input
Terminal
Designation
Function
Jumper
Input
Terminal
Designation
Function
Jumper
10
1
C10
GND
X20
5
1
C5
GND
X15
2
L10
+24 V
2
L5
+24 V
9
3
C9
GND
X19
4
3
C4
GND
X14
4
L9
+24 V
4
L4
+24 V
8
5
C8
GND
X18
3
5
C3
GND
X13
6
L8
+24 V
6
L3
+24 V
7
7
C7
GND
X17
2
7
C2
GND
X12
8
L7
+24 V
8
L2
+24 V
6
9
C6
GND
X16
1
9
C1
GND
X11
10
L6
+24 V
10
L1
+24 V