27
Ambient temperature:
+0 °C to +40 °C
Recommended tempe15 °C to +25 °C
Storage temperature:
-15 °C to +50 °C
Cooling:
Forced air-cooling
Humidity:
0-95%, non-condensing
Audible noise:
< 45 db normal and battery mode (700-1000 VA)
< 50 db normal and battery mode (1500-3000 VA)
STANDARDS
Safety: EN50091-1-1
Emissions:
EN50091-2 class B
Immunity: EN50091-2
OUTPUT
POWER
700VA/490 W
1000VA/700W 1500VA/1050W 2000VA/1400W 3000VA/2100W
Connection
Input
IEC 320 (10A)
IEC 320 (10A)
IEC 320 (10A)
IEC 320 (10A)
IEC 320 (16A)
4 x IEC 320
(10A)
4 x IEC 320
(10A)
4 x IEC 320
(10A)
8 x IEC 320
(10A), 1 x IEC
320 (16A)
8 x IEC 320
(10A), 1 x IEC
320 (16A)
4 x 5-15R (US) 4 x 5-15R (US) 4 x 5-15R (US) 12 x 5-15R (US) 12 x 5-15R (US)
Connection
Output
2 x Europe
2 x Europe
2 x Europe
6 x Europe, 1 x
IEC 320 (16A)
6 x Europe, 1 x
IEC 320 (16A)
Battery type
Lead-acid
7.2Ah/12V
Lead-acid
7.2Ah/12V
Lead-acid
9Ah/12V
Lead-acid
7.2Ah/12V
Lead-acid
9Ah/12V
Number of
batteries
2
3
3
6
6
Backup
time/full
load
5 min
6 min
5 min
6 min
5 min
Recharge
time
<4 hours to 90% <4 hours to 90% <4 hours to 90% <4 hours to 90% <4 hours to 90%
Dimensions
W x D x H
mm
152 x 420 x 238 152 x 420 x 238 152 x 420 x 238 225 x 425 x 360 225 x 425 x 360
Weight kg
13.5
16.2
17
31.6
33
Summary of Contents for ROLINE ProSecure II 1000 VA
Page 1: ...I ROLINE ProSecure II 700 1000 1500 2000 3000VA Standger t 19 Rack 1HE 2HE Bedienungsanleitung...
Page 14: ...8 R ckseitenansichten...
Page 15: ...9...
Page 30: ...ProSecure II 700 VA 3000 VA UPS User s and Installation Manual...
Page 44: ...14 Rear panel views PROSECURE II 700 1 5KVA REAR PANEL PROSECURE II 2 3KVA REAR PANEL...