26
Technical Specifications
Power Range 700-3000 VA
GENERAL
Rated power
700VA, 1000 VA, 1500 VA, 2000 VA,
3000 VA at p.f 0.7
Technology
On-line, double conversion topology with automatic bypass
INPUT
Phase
Single phase with ground
Bypass Voltage:
184-265 VAC (user selectable)
Input Voltage range:
120/140/160 VAC-276 VAC
Frequency:
50/60 Hz. Auto selection
Frequency window from mains
45-65 Hz
Synchronization window
± 3Hz.
Input current
700 VA 3A, 1000 VA 4A, 1500 VA 5.7A,
2000 VA 7.7A, 3000 VA 12A
Input Power factor:
0.97
OUTPUT
Output Voltage:
208/220/230/240 VAC, selectable from LCD panel
Voltage regulation:
± 2%
Voltage distortion:
< 5% THD at full non-linear load, < 3% THD at full linear load
Frequency regulation
± 0.25 Hz (battery or free running mode)
* 120V at 40% load, 140V at 70%, 160V at 100%.
Dynamic response:
± 9 % max from 100% to 20 % or from 20% to 100 % linear load
Overload capacity:
100-125% 1 min, 125-150% 10 sec
Efficiency:
greater than 86%
Power Range 700-3000 VA (19” Rack-mount model)
GENERAL
Rated power
700VA, 1000 VA, 1500 VA, 2000 VA,
3000 VA at p.f 0.7
Technology
On-line, double conversion topology with automatic bypass
INPUT
Phase
Single phase with ground
Bypass Voltage:
184-265 VAC (user selectable)
Input Voltage range:
120/140/160 VAC-276 VAC
Frequency:
50/60 Hz. Auto selection
Frequency window from mains
45-65 Hz
Synchronization window
± 3Hz.
Input current
700 VA 3A, 1000 VA 4A, 1500 VA 5.7A,
2000 VA 7.7A, 3000 VA 12A
Input Power factor:
0.97
OUTPUT
Output Voltage:
208/220/230/240 VAC, selectable from LCD panel
Voltage regulation:
± 2%
Voltage distortion:
< 5% THD at full non-linear load, < 3% THD at full linear load
Frequency regulation
± 0.25 Hz (battery or free running mode)
* 120V at 40% load, 140V at 70%, 160V at 100%.
Dynamic response:
± 9 % max from 100% to 20 % or from 20% to 100 % linear load
Overload capacity:
100-125% 1 min, 125-150% 10 sec
Efficiency:
greater than 86%
Summary of Contents for ROLINE ProSecure II 1000 VA
Page 1: ...I ROLINE ProSecure II 700 1000 1500 2000 3000VA Standger t 19 Rack 1HE 2HE Bedienungsanleitung...
Page 14: ...8 R ckseitenansichten...
Page 15: ...9...
Page 30: ...ProSecure II 700 VA 3000 VA UPS User s and Installation Manual...
Page 44: ...14 Rear panel views PROSECURE II 700 1 5KVA REAR PANEL PROSECURE II 2 3KVA REAR PANEL...