950-0207revA - 15 - November 27, 2013
CAUTION:
● Adjust the height by screwing the nut with a spanner.
● Inset the spanner into the hanger bracket through the interspace. See Fig. 9 below.
It is possible to install hanger brackets by not removing the brackets from the indoor unit.
See Fig. 10 below.
Only the specified accessories and parts for installation work could be use.
When installing the indoor unit, you can refer the paper pattern for installation. Make sure that the
drainage side
MUST BE
0.4
”lower than the other side in order to drain the condensate water easily.
CAUTION:
a. Prior to the installation, please make a good preparation for all piping (refrigerant pipe, drain pipe)
and wring (wires of the wall control, connection cables between the indoor and outdoor unit) of the
indoor unit to make the further installation much easier.
b. If there is an opening in the ceiling, it is better to reinforce it to keep it flat and prevent it vibrating.
Consult the user and builder for more details.
c. If the strength of the ceiling is not strong enough, a beam made of angle iron can be used and
then fix the unit on it.
d. If the indoor unit is not installed in the air conditioning area, please use sponge around the unit to
prevent condensing. The thickness of the sponge depends on the actual installation environment.
INSTALLING THE CONDENSATE PIPE
1. Drain piping
● Either the right rear or right side of the unit is suitable for fixing the drainpipe.
● The diameter of the drainpipe should be equal to or greater than that of the connecting pipe.
● The condensate pipe should keep an inclination angle of 5° to 10°, which can facilitate the
drainage of the condensate water. And
the joints of the condensate pipe should
be insulated by the insulation material to
prevent condensing. See Fig. 11
Figure 11
.
Thermal Insulation of the Condensate Pipe