background image

SCOTSMAN WOOD FURNACE – INSTRUCTION MANUAL 

 

Scotsman

 

 

Jun

-10

 

5

1.4  MAXIMUM SOLID-FUEL CHARGE 

 

The maximum level for a solid-fuel charge is the middle of the loading door, or the level of the 
handle.  DO NOT OVERFILL.  The furnace will accept whole or split logs up to 34 in. (865 mm) 
long, but a 30 in. (765 mm) log length is recommended for convenience and ease in handling. 

 

Maximum damper gate opening is 11/16”.  Do not tamper or adjust to greater opening in an 
attempt to increase fire or over-firing and hazard may result. 

 

1.5 MAINTENANCE 

 

Some regular maintenance is necessary on the furnace.  A good practice is to establish a 
routine for the storage of fuel, care of the appliance and firing techniques. 

 

1.5.1 CLEANING

 (Fig. S101-14)

 

 

The furnace must be cleaned regularly to maintain top efficiency.  The furnace needs cleaning 
more often when burning green wood, or during long periods of low fire.  When the furnace is 
first installed the heat exchanger should be checked visually from the firebox and smoke pipe 
hole every week to determine the rate at which creosote or ash is accumulating within the 
furnace.  Cleaning should be done whenever there is more than 1/4 inch of build-up on the 
heat exchanger or 3 inches of ash in the base.  If the wood furnace is to be left unused for an 
extended period of time (more than one month) then the appliance should be cleaned of all 
ash and residual left from the burning of wood. 

 

CLEANING PROCEDURE 

 

o

  Make sure fire is completely out and the furnace has cooled. 

o

  Remove the cleanout cover, located on the rear of the furnace heat exchanger, the 

smoke pipe, and internal breech baffle. 

o

  The heat exchanger is now accessible for cleaning. 

o

  Use the scraper provided to remove all soot and ash from the furnace heat exchanger 

and exposed surfaces. 

o

  Scrape all residues in the top heat exchanger towards the rear of the furnace where it will 

fall into the firebox. 

o

  Always check flue pipe for creosote or ash build-up in the pipe and clean if necessary. 

o

  Reinstall cleanout cover, internal breech baffle (See section 2.4.2) and smoke pipe 

making sure that all joints are secured with at least 3 sheet metal screws. 

o

  Check chimney cleanout for ash build-up and remove any accumulation. 

o

  Residue may be removed from the firebox or left to be burnt during the next fire.  It is 

good practice to leave a layer of ash approximately one inch deep in the base of the 
firebox. 

 
 
 
 
 
 
 
 
 
 

Summary of Contents for DB-101

Page 1: ...RE INSTALLING FURNACE OR LIGHTING FIRE CONSULT LOCAL AUTHORITIES IF IN DOUBT ABOUT YOUR LOCAL FIRE SAFETY REGULATIONS ALL INSTALLATIONS MUST BE MADE IN ACCORDANCE WITH LOCAL AND STATE OR PROVINCIAL CO...

Page 2: ...t 17 Appendices APPENDIX A Warranty DIAGRAMS S101 1 Add On to Oil Clearances S101 2 Add On to Oil S type duct S101 3 Gravity Return Air Kit S101 4 Base for use on Combustible Floor S101 5 Controls Pla...

Page 3: ...h 36 Diameter 23 Secondary Heat Exchanger 14 gauge steel Fire Box Door Cast Iron 13 x 13 Warm Air Plenum 32 x 25 3 8 Return Air Plenum N A Air Filter Size 16 x 20 x 1 Blower Size G10 10 Blower Motor 1...

Page 4: ...anufactured logs compressed wood Before adding fuel to an existing fire turn up the thermostat for about five minutes or lift damper chain to hold damper fully open for about one minute before opening...

Page 5: ...s smoke pipe and chimney allowing large amounts of creosote to form To reduce creosote build up during periods of low heat requirements i e Spring and Fall it is recommended to fuel the wood furnace w...

Page 6: ...Cleaning should be done whenever there is more than 1 4 inch of build up on the heat exchanger or 3 inches of ash in the base If the wood furnace is to be left unused for an extended period of time m...

Page 7: ...the following precautions should be taken DO NOT shut off power The blower must be kept running to disperse excessive heat Manually close the damper door by unhooking the chain Check controls for pro...

Page 8: ...he cover is an option available from your Kerr dealer The kit must be installed on the cabinet side directly opposite to the entry of the blower or oil furnace S connection ductwork Manually open the...

Page 9: ...fuel within the above clearances or within the space required for charging and ash removal o Establish a routine for storage of fuel care of the appliance and firing techniques 2 0 INSTALLATION INSTRU...

Page 10: ...ig S101 4 The location of the furnace must be as close as possible to the tile lined brick chimney or factory built solid fuel approved chimney ULC S629 Keep in mind also the day to day operation and...

Page 11: ...e flue gases are forced to fully heat the secondary heat exchanger which will maintain higher furnace efficiency The furnace must be located to meet a minimum venting distance needed between the furna...

Page 12: ...lue key pipe dampers and check draft controls located on or in the flue pipe 4 The flue pipes of the appliances are connected to a manifold as close to the chimney as practicable or directly to the ch...

Page 13: ...duct a 2 51 mm minimum clearance must be maintained between the warm air supply ducts and all joists or combustible material See Fig S101 1 Return air ducts including main ducts and branch ducts on s...

Page 14: ...m the yellow wire leading to the blower compartment and both red and yellow wires marretted off then there would be no need for the switching relay Honeywell R4222D 1013 or equiv In that case the two...

Page 15: ...end of the wire on to the other side of the normally open contacts relay spade 3 8 Remove the yellow low speed wire from the blower motor this should be the selected low speed in the furnace wiring bo...

Page 16: ...a reverse flow is possible Before attempting installation determine if there is suitable space available in the furnace area for the furnace connection outlined herein The external static pressure in...

Page 17: ...h technicians shall be licensed to perform this service The installation shall comply with the applicable requirements of CSA standard B365 Installation Code for Solid Fuel Burning Appliances and Equi...

Page 18: ...s main disconnect switch within view 2 Wiring cables protected from heat and not touching hot surfaces FLUE AND SMOKE PIPE INSPECTION 1 Flue inner size equivalent to 7 round or larger 2 Separate entry...

Page 19: ...ON CAPABILITY Add on furnaces such as the Kerr Scotsman and Scotty SS can be installed with oil fired warm air furnaces such as the Kerr Gemini that have continuous blower circulation capability A rel...

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ......

Reviews: