background image

SCOTSMAN WOOD FURNACE – INSTRUCTION MANUAL 

 

Scotsman

 

 

Jun

-10

 

10

2.4.1 COMBUSTION AIR SUPPLY 

 

Air inlets of at least 200 square inches free area (1.5 in

2

/1000Btu) must be provided to the 

room occupied by the wood fired or oil fired furnace.  These fresh air inlets must provide or 
allow free access of fresh outside air to the furnace.  At no time or under any circumstances 
can a wood or oil-burning appliance be starved of combustion air. 

 

The appliance must at all times be able to maintain the approved stack draft.  The barometric 
draft regulator must be installed on the furnace smoke pipe in the same room or at least in 
such a way that there is unrestricted free passage of air between the combustion air inlet to the 
furnace or burner and the barometric draft regulator. 

 

It is important to provide adequate combustion air to the furnace.  It may be necessary to add a 
ventilator to an exterior wall of a closed furnace room or an airtight basement. 

 

Operating a wood or oil fired appliance with inadequate combustion air could be hazardous. 

 

2.4.2 FLUE PIPE & CHIMNEY 

 

The internal breech baffle should be inserted through the breech towards the front of the 
furnace until it hits the internal baffle stop.  The open slot running the length of the baffle 
should be located on the top.  This baffle is removed during the cleaning procedure.  The 
purpose of the baffle is to prevent short-circuiting of the flue gases out through the rear breech.  
The flue gases are forced to fully heat the secondary heat exchanger, which will maintain 
higher furnace efficiency. 

 

The furnace must be located to meet a minimum venting distance needed between the furnace 
and the flue.  It should also be ducted so that there are a minimum number of elbows used.  
The flue pipe must be installed with a gradual rise of 1/2” or more per foot from the furnace to 
the flue. 

 

NEVER ALLOW THE SMOKE PIPE TO RUN DOWNHILL TO THE FLUE! 

 

The smoke pipe and chimney should be at least 7 inches in diameter.  The flue pipe or a 
chimney may be of different cross-sectional area than that of the appliance smoke pipe, 
provided that sufficient draft is available at the appliance.  Space must be provided around the 
smoke pipe and the back of the furnace to allow easy access for the purpose of cleaning.  
Smoke pipes must not be lighter than 24 gauge black steel.  All pipes must be securely 
fastened with at least 3 sheet metal screws at every joint, and properly supported. 

 

Always meet or exceed flue pipe clearance specifications - 18” clearance from flue pipe to 
combustibles in all directions. 

 

Connect the furnace only to an approved chimney suitable for solid fuel appliances and 
capable of venting the products of combustion.  The chimney must be installed with proper 
clearances above roof and from adjacent structures and trees.  If a masonry chimney is used it 
must be in good condition and be equipped with a tile liner.  Flue thimble or flue pipe must not 
extend into the chimney flue, as it will reduce the draft. 

 

Connect only to a flue or chimney capable of maintaining a negative draft of .05” wc at all times 
and conditions. 

 

Summary of Contents for DB-101

Page 1: ...RE INSTALLING FURNACE OR LIGHTING FIRE CONSULT LOCAL AUTHORITIES IF IN DOUBT ABOUT YOUR LOCAL FIRE SAFETY REGULATIONS ALL INSTALLATIONS MUST BE MADE IN ACCORDANCE WITH LOCAL AND STATE OR PROVINCIAL CO...

Page 2: ...t 17 Appendices APPENDIX A Warranty DIAGRAMS S101 1 Add On to Oil Clearances S101 2 Add On to Oil S type duct S101 3 Gravity Return Air Kit S101 4 Base for use on Combustible Floor S101 5 Controls Pla...

Page 3: ...h 36 Diameter 23 Secondary Heat Exchanger 14 gauge steel Fire Box Door Cast Iron 13 x 13 Warm Air Plenum 32 x 25 3 8 Return Air Plenum N A Air Filter Size 16 x 20 x 1 Blower Size G10 10 Blower Motor 1...

Page 4: ...anufactured logs compressed wood Before adding fuel to an existing fire turn up the thermostat for about five minutes or lift damper chain to hold damper fully open for about one minute before opening...

Page 5: ...s smoke pipe and chimney allowing large amounts of creosote to form To reduce creosote build up during periods of low heat requirements i e Spring and Fall it is recommended to fuel the wood furnace w...

Page 6: ...Cleaning should be done whenever there is more than 1 4 inch of build up on the heat exchanger or 3 inches of ash in the base If the wood furnace is to be left unused for an extended period of time m...

Page 7: ...the following precautions should be taken DO NOT shut off power The blower must be kept running to disperse excessive heat Manually close the damper door by unhooking the chain Check controls for pro...

Page 8: ...he cover is an option available from your Kerr dealer The kit must be installed on the cabinet side directly opposite to the entry of the blower or oil furnace S connection ductwork Manually open the...

Page 9: ...fuel within the above clearances or within the space required for charging and ash removal o Establish a routine for storage of fuel care of the appliance and firing techniques 2 0 INSTALLATION INSTRU...

Page 10: ...ig S101 4 The location of the furnace must be as close as possible to the tile lined brick chimney or factory built solid fuel approved chimney ULC S629 Keep in mind also the day to day operation and...

Page 11: ...e flue gases are forced to fully heat the secondary heat exchanger which will maintain higher furnace efficiency The furnace must be located to meet a minimum venting distance needed between the furna...

Page 12: ...lue key pipe dampers and check draft controls located on or in the flue pipe 4 The flue pipes of the appliances are connected to a manifold as close to the chimney as practicable or directly to the ch...

Page 13: ...duct a 2 51 mm minimum clearance must be maintained between the warm air supply ducts and all joists or combustible material See Fig S101 1 Return air ducts including main ducts and branch ducts on s...

Page 14: ...m the yellow wire leading to the blower compartment and both red and yellow wires marretted off then there would be no need for the switching relay Honeywell R4222D 1013 or equiv In that case the two...

Page 15: ...end of the wire on to the other side of the normally open contacts relay spade 3 8 Remove the yellow low speed wire from the blower motor this should be the selected low speed in the furnace wiring bo...

Page 16: ...a reverse flow is possible Before attempting installation determine if there is suitable space available in the furnace area for the furnace connection outlined herein The external static pressure in...

Page 17: ...h technicians shall be licensed to perform this service The installation shall comply with the applicable requirements of CSA standard B365 Installation Code for Solid Fuel Burning Appliances and Equi...

Page 18: ...s main disconnect switch within view 2 Wiring cables protected from heat and not touching hot surfaces FLUE AND SMOKE PIPE INSPECTION 1 Flue inner size equivalent to 7 round or larger 2 Separate entry...

Page 19: ...ON CAPABILITY Add on furnaces such as the Kerr Scotsman and Scotty SS can be installed with oil fired warm air furnaces such as the Kerr Gemini that have continuous blower circulation capability A rel...

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ......

Reviews: