Operational Characteristics 1300 lb system
Cycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F
System Pressures @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.
Headmaster maintains a minimum discharge
pressure during freeze of:
·
217 PSIG + 25, -15 PSIG
CPR Valve Setting: 55 - 60 PSIG.
Note: CPR allows a maximum low side pressure at
the CP unit’s compressor. Maximum only occurs
during harvest.
Refrigerant Charge
·
288 oz
Compressor Amps
·
Single Phase - 15
·
Three Phase - 8
Batch Weight
·
16 lb
Discharge Pressure Cut Out Switch
·
Cuts Out at: 450 PSIG
·
Resets at: 350 PSIG
Compressor: CS20K6E
Expansion Valves: 1
Eclipse
ä
1300, 1600
September 2003
Page 44
70/70/50
90/90/70
120/110/100
Freeze
12 to 13 minutes
16 to 17 minutes
26 to 28 minutes
Harvest
3 minutes
2 minutes
1 minute
70/70/50
90/90/70
120/110/100
Suction at Ice Making Section, end of Freeze
30 to 34 PSIG
32 to 36 PSIG
40 to 44 PSIG
Suction at Ice Making Section, Harvest
70 to 80 PSIG
90 to 110 PSIG
120 to 140 PSIG
Discharge at Condensing Unit: Freeze
230 to 250 PSIG
250 to 270 PSIG
370 to 390 PSIG