Service Diagnosis
Eclipse
ä
1300, 1600
September 2003
Page 40
Problem or Symptom
Possible Cause
Probable Correction
No ice
No power to ice making section
Restore power
No power to condensing unit
Restore power
No lights on controller
Check transformer
Unit manually switched off
Push and release the Freeze button, ask
user why it was shut off
Power to both sections, controller reset,
but condensing unit does not operate
Interconnecting control wire
disconnected, reconnect it
Low or high pressure cut outs open,
check system pressures
No water to ice making section, controller
blinking water light twice and repeating
Restore water supply, check water filters,
reset controller
Check inlet water valve operation
Check water level sensor operation,
including harness between sensor and
controller*
Ice making section has exceeded
maximum freeze time and controller has
shut down the system
Condenser coils may need cleaning
Check condenser fan blade and motor
Check for excessive air intake
temperatures at condenser coil
Check compressor contactor
Check compressor and starting
components
Check water pump
Check purge valve for leak through
Check vapor inlet valve for leak though
Ice making section has exceeded
maximum harvest time and shut down the
system
Check ice making section for lime scale
build up, clean as needed
Check condenser by pass valve
Check vapor inlet valve*
Check headmaster
Check ice sensors for cube sensing*
Check inlet water valve for leak through
Check for obstruction in ice delivery chute
Bin full light is on but bin is not full
Check ice sensors*
Check thermostat*
* Additional diagnostics for this component are on the following pages