Top vent must be a minimum size of
220mm x 90mm and no more than
200mm from top of door
Vent
Vent must have a minimum of
60mm of air space behind
door for air flow out of cabinet
Bottom cut out of the cabinet
must be at least 200mm x
40mm
The measurements given are the minimum sizes required to provide sufficient air flow to cool the compressor, any
less air flow and the units capacity will be effected.
If there is not enough room to place the right size vents or
the cabinet temp is reaching over 27
o
C
the cabinet will need to be vented using a fan forced system to provide enough air flow.
WARNING
Venting requirements