L-01412-4-04 

!

 

 Remove the emergency battery from the lid. 

 

 Insert a new emergency battery into the lid. 

 

 Return the battery fixing bracket to the original position and screw down. Check that the battery is 

positioned securely. 

 

 Remove the protective cap of the battery connector. 

 

 Attach the battery connector to the socket in the battery box. Check the catch mechanism of the 

plug connection. 

 

 Alert the emergency light unit to the presence of a new battery: 

Open and close the lid of the battery box twice within a 60-second period. Opening and closing the 
case must occur within 10 seconds of each other. During this time the emergency electronic unit 
must be supplied by the mains supply. 
If this procedure is done correctly, immediately after the battery box is closed for the second time, 
the signal LED will display an acknowledgement light. The five-second long red-green 
acknowledgement light confirms that a operational life test will be conducted 12 hours later. 

 

 Close the lid of the battery box with the screw plug. 

 

Should a battery capacity fault be present when the acknowledgement light is displayed, more 
operational life tests will then be carried out at 52 week intervals. If no fault was detected in the battery 
capacity, the interval until the next regular operational life test is unaffected. 

 

6.4  Replacing emergency light unit and LED-reflector 

 

Replacement of the emergency light unit and LED-reflector with mounted LED-modules has been 
described in the separate instructions which can be found attached to the spare parts to be 
supplied. 

 

6.5  Environmental advice 

 

This device has got an accumulator which among other things contains 
cadmium which is ecologically dangerous. There is a particular 
designation for this purpose.  
The people operating this device are obliged by law to return 
accumulators which have become waste and which contain any pollutant 
materials to organizations which are in the hands of the vendors or 
waste disposal holders being under public law. 

 

6.6  Placing the fitting out of operation 

 

To place the light fitting out of operation the battery must be separated from the emergency light unit.

  

In order to avoid unnecessarily removing the emergency battery, disconnection should take place 
immediately after the interruption of the power supply.

 

 

During storage there will also be a gradual discharge of the battery. If the voltage drops below a 
certain level the battery will no longer be detected by the emergency electronic. Thus a battery contact 
failure will be indicated although the connection to the battery still exists

In this case, the emergency 

battery is to be removed as described in Section 6.3 and to be charged separately from the light fitting. 
With a 6V charging voltage and 80 mA charging current, a discharged battery will be sufficiently 
charged within just 5 minutes for it to be reinserted into the light fitting, where it can continue to charge.  

 

  To avoid any damages the battery should not be stored for more than 6 months 

without being re-charged periodically! 

 

 

 
 

Summary of Contents for e864 12L Series

Page 1: ...ends on the observance of all safety standards Exact knowledge about all applicable regulations and standards is mandatory for installation maintenance and repair of explosion proof equipment especial...

Page 2: ...ubject to any kind of vibrations it is highly recommended to consult the Adolf Schuch GmbH before starting the installation Every structural modification will cause dangerous situations and consequent...

Page 3: ...up of a series connection which itself is built up of parallel connections of single LEDs Failures of LEDs do not necessarily lead to a change in the power consumption which is recognized by the emerg...

Page 4: ...itions after a correctly performed switching sequence at L1 terminal an operational life test is immediately initiated If the switching sequence is correctly carried out on L1 terminal an operational...

Page 5: ...connection between the emergency light unit and the battery is re established 2 4 LED Signals The two colored LED red green which is integrated in the reflector of the light fitting does show the work...

Page 6: ...the light fitting 3 Technical Data Series e864 12L Capacity of emergency battery Nominal operating time in case of emergency Index of luminous flux Explosion proof LED Emergency Light Fitting for oper...

Page 7: ...ion position in any direction except upwards light output Rated luminous flux ca 16 with e864 12L42 ca 12 with e864 12L60 Spare battery Typ 8020 6 V 1 6 Ah NiCd 1 hour emergency light time standard ve...

Page 8: ...fitting in an explosive dust atmosphere is depending on the properties of the surrounding dust Please ensure that there will be an adequate difference between the maximum surface temperature of the f...

Page 9: ...es which are not used must be closed with the enclosed closure plug Torque see Chapter 3 Technical Data An inlaid dust protective disc if existing must be removed before The conductors must not be dam...

Page 10: ...elivery state there is no electrical connection between the emergency battery and the emergency light unit If no power supply is present even if the light fitting is connected to the emergency battery...

Page 11: ...k and ensure that the light fitting has been installed according to the regulations and in the allowed operating position the explosion proof cable glands resp explosion proof locking screws are secur...

Page 12: ...s in 3 phase circuits and with a common neutral conductor N Light fittings with emergency light unit OK fault If the common neutral conductor is interrupted and voltage is present then light fittings...

Page 13: ...have got thermal insulation characteristic features It is necessary to clean the fitting from dust regularly In case the dust layer may be higher than 5 mm it must be ensured that the surface tempera...

Page 14: ...ctor with mounted LED modules has been described in the separate instructions which can be found attached to the spare parts to be supplied 6 5 Environmental advice This device has got an accumulator...

Page 15: ...L 014124 04 15...

Page 16: ...16 L 01412 4 04 The test certificates are ready to be loaded down from our homepage www schuch de or we shall send it on request Misprints modifications and errors are excepted...

Reviews: