1.   Safety Instructions 

 

 

Mounting and installation must be done in accordance with the respective regulations.  

 

 

The light fitting must be protected against overvoltage, overcurrent, short circuits and other 
electrical failures. 

 

 

The light fitting must be operated in an undamaged condition only.  

 

 

The light fitting may only be opened if it has been completely disconnected from the mains supply 
and the plug connector of the battery in the battery box is disconnected! 

 

 

The non-stationary use of the light fitting as well as any other inappropriate usage is prohibited. 

 

 

The operation of the light fitting is allowed within its assessment thresholds only. 

 

 

In regard to the minimum and maximum admissible ambient temperature potential sources of cold 
and heat (e.g. direct heat or solar radiation, cooling units) have to be considered. 

 

 

If the light fitting is subject to a special application that is influenced chemically, mechanically, 
thermically or electrically or if the light fitting will be subject to any kind of vibrations, it is highly 
recommended to consult the Adolf Schuch GmbH before starting the installation. 

 

 

Every structural modification will cause dangerous situations and consequently the certification of 
this light fitting will be null and void. So it is not allowed to drill through the housing for installation 
purposes. 

 

 

Caution - Risk of electrostatic discharge! Fitting to be cleaned with damp cloth only! 

 

 

In areas with risk of accidental electrostatic charge (e.g. by passing by) the light fitting must be 
protected by appropriate measures.  

 

 

The light fitting is not allowed to be installed in process areas where strong electrical fields may 
occur (i.e. HV Sparkling Electrodes or Particle Streams). Reason is to avoid any electrostatic 
charge of the light fitting itself. 

 

 

Replace damaged explosion-proof parts by original spare parts from the Adolf Schuch GmbH only. 

 

 

LED-reflector with mounted LED-modules and Electronic control gear of this light fitting must be 
replaced by A. Schuch GmbH, by a service technician who is instructed from Schuch or by any 
other person with equivalent qualification only.  
It is not allowed to replace the individual LED-modules of this light fitting. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

Summary of Contents for e864 12L Series

Page 1: ...ends on the observance of all safety standards Exact knowledge about all applicable regulations and standards is mandatory for installation maintenance and repair of explosion proof equipment especial...

Page 2: ...ubject to any kind of vibrations it is highly recommended to consult the Adolf Schuch GmbH before starting the installation Every structural modification will cause dangerous situations and consequent...

Page 3: ...up of a series connection which itself is built up of parallel connections of single LEDs Failures of LEDs do not necessarily lead to a change in the power consumption which is recognized by the emerg...

Page 4: ...itions after a correctly performed switching sequence at L1 terminal an operational life test is immediately initiated If the switching sequence is correctly carried out on L1 terminal an operational...

Page 5: ...connection between the emergency light unit and the battery is re established 2 4 LED Signals The two colored LED red green which is integrated in the reflector of the light fitting does show the work...

Page 6: ...the light fitting 3 Technical Data Series e864 12L Capacity of emergency battery Nominal operating time in case of emergency Index of luminous flux Explosion proof LED Emergency Light Fitting for oper...

Page 7: ...ion position in any direction except upwards light output Rated luminous flux ca 16 with e864 12L42 ca 12 with e864 12L60 Spare battery Typ 8020 6 V 1 6 Ah NiCd 1 hour emergency light time standard ve...

Page 8: ...fitting in an explosive dust atmosphere is depending on the properties of the surrounding dust Please ensure that there will be an adequate difference between the maximum surface temperature of the f...

Page 9: ...es which are not used must be closed with the enclosed closure plug Torque see Chapter 3 Technical Data An inlaid dust protective disc if existing must be removed before The conductors must not be dam...

Page 10: ...elivery state there is no electrical connection between the emergency battery and the emergency light unit If no power supply is present even if the light fitting is connected to the emergency battery...

Page 11: ...k and ensure that the light fitting has been installed according to the regulations and in the allowed operating position the explosion proof cable glands resp explosion proof locking screws are secur...

Page 12: ...s in 3 phase circuits and with a common neutral conductor N Light fittings with emergency light unit OK fault If the common neutral conductor is interrupted and voltage is present then light fittings...

Page 13: ...have got thermal insulation characteristic features It is necessary to clean the fitting from dust regularly In case the dust layer may be higher than 5 mm it must be ensured that the surface tempera...

Page 14: ...ctor with mounted LED modules has been described in the separate instructions which can be found attached to the spare parts to be supplied 6 5 Environmental advice This device has got an accumulator...

Page 15: ...L 014124 04 15...

Page 16: ...16 L 01412 4 04 The test certificates are ready to be loaded down from our homepage www schuch de or we shall send it on request Misprints modifications and errors are excepted...