cutoff switch must also be closed. 

 

Automatic operational life tests: 
The first operational life test carried out automatically by the emergency light unit takes place at 
random within a period of 5 to 28 days after the light fitting has been setup. All further automatic 
operational life tests are then carried out at 52 week intervals, so long as the energy supply to the 
emergency light unit was not interrupted during this period.  
A complete interruption of the energy supply to the emergency light unit occurs when the outage of the 
power supply exceeds the specified nominal operating time for the emergency light.  
Reconnecting the power supply to the emergency light unit after a complete interruption will lead to a 
new setup procedure of the emergency light with a subsequent operational life test between 5 and 28 
days later. 
Should a fault in the battery capacity be indicated before a complete interruption of the power supply to 
the emergency light unit, a operational life test will be carried out within 24 hours of reconnection to the 
power supply. 
If the prerequisites stated above for carrying out an automatic operational life test are not satisfied, the 
test will be deferred until these requirements are fulfilled.  
Automatic operational life tests that could not be completed successfully will be repeated once after 60 
hours, subject to the same prerequisites stated above. 

 

Manual operational life tests: 
Operational life tests can be triggered manually in 3 ways: 

 

1. By switching the power supply off and on at the L1 terminal. 
2. By switching the supply on and off at the L1` terminal. 

 

Switch the power supply at the L1 terminal resp. the supply at L1' terminal off and on again 5 times. 
Leave at least 2 seconds between each switch.

 

In both cases, the sequence of switches must be completed within 60 seconds. 
Under the above mentioned preconditions, after a correctly performed switching sequence at L1' 
terminal, an operational life test is immediately initiated.  
If the switching sequence is correctly carried out on L1 terminal, an operational life test is initiated after 
the time that is required to fully charge the battery after the switching sequence.  
If the switch sequence has not been carried out correctly, or the aforementioned requirements have 
not been satisfied, the operational life test will not be conducted.  
If there was an error in the switching procedure, the entire switch sequence can only be repeated after 
60 seconds have elapsed. 
The points at which regular operational life tests are carried out are not affected by conducting a 
manual test using either of these methods.  

 

3. By means of disconnecting and reconnecting the battery: 
Open and close the lid of the battery box twice within a 60-second period. Opening and closing the 
case must occur within 10 seconds of each other.  

If this procedure is done correctly, immediately after the battery box is closed for the second time, the 
signal LED will display an acknowledgement light. The five-second long red-green acknowledgement 
light confirms that a operational life test will be conducted 12 hours later. 
Should a battery capacity fault be present when the acknowledgement light is displayed, more 
operational life tests will then be carried out at 52 week intervals. If no fault was detected in the battery 
capacity, the interval until the next regular operational life test is unaffected. 

 

  During the functionality and operational life tests, the light fitting will switch on even if it 

was previously switched off!

 

 

 

 

2.3   Ascertainable faults and reset of the display 

 

LED failure 
If a fault in the LED is detected by the emergency light unit during a functionality test, the LEDs will be 
switched off and the fault will be indicated by a permanent red light on the signal LED. 
An LED fault will be reset if a functionality test produces a positive result or if the emergency light unit 
is completely separated from the battery and power supply.  

Summary of Contents for e864 12L Series

Page 1: ...ends on the observance of all safety standards Exact knowledge about all applicable regulations and standards is mandatory for installation maintenance and repair of explosion proof equipment especial...

Page 2: ...ubject to any kind of vibrations it is highly recommended to consult the Adolf Schuch GmbH before starting the installation Every structural modification will cause dangerous situations and consequent...

Page 3: ...up of a series connection which itself is built up of parallel connections of single LEDs Failures of LEDs do not necessarily lead to a change in the power consumption which is recognized by the emerg...

Page 4: ...itions after a correctly performed switching sequence at L1 terminal an operational life test is immediately initiated If the switching sequence is correctly carried out on L1 terminal an operational...

Page 5: ...connection between the emergency light unit and the battery is re established 2 4 LED Signals The two colored LED red green which is integrated in the reflector of the light fitting does show the work...

Page 6: ...the light fitting 3 Technical Data Series e864 12L Capacity of emergency battery Nominal operating time in case of emergency Index of luminous flux Explosion proof LED Emergency Light Fitting for oper...

Page 7: ...ion position in any direction except upwards light output Rated luminous flux ca 16 with e864 12L42 ca 12 with e864 12L60 Spare battery Typ 8020 6 V 1 6 Ah NiCd 1 hour emergency light time standard ve...

Page 8: ...fitting in an explosive dust atmosphere is depending on the properties of the surrounding dust Please ensure that there will be an adequate difference between the maximum surface temperature of the f...

Page 9: ...es which are not used must be closed with the enclosed closure plug Torque see Chapter 3 Technical Data An inlaid dust protective disc if existing must be removed before The conductors must not be dam...

Page 10: ...elivery state there is no electrical connection between the emergency battery and the emergency light unit If no power supply is present even if the light fitting is connected to the emergency battery...

Page 11: ...k and ensure that the light fitting has been installed according to the regulations and in the allowed operating position the explosion proof cable glands resp explosion proof locking screws are secur...

Page 12: ...s in 3 phase circuits and with a common neutral conductor N Light fittings with emergency light unit OK fault If the common neutral conductor is interrupted and voltage is present then light fittings...

Page 13: ...have got thermal insulation characteristic features It is necessary to clean the fitting from dust regularly In case the dust layer may be higher than 5 mm it must be ensured that the surface tempera...

Page 14: ...ctor with mounted LED modules has been described in the separate instructions which can be found attached to the spare parts to be supplied 6 5 Environmental advice This device has got an accumulator...

Page 15: ...L 014124 04 15...

Page 16: ...16 L 01412 4 04 The test certificates are ready to be loaded down from our homepage www schuch de or we shall send it on request Misprints modifications and errors are excepted...

Reviews: