4.2   Electrical connection 

 

 

 Screw the explosion-proof cable glands and explosion-proof locking screw supplied with the fitting 

into the borings of the housing by using the lock nuts (Torques see Chapter 3, Technical Data). 

 

 

After mounting the light fitting housing insert the connection cable through the explosion-proof cable 
gland. An inlaid dust protective disc, if existing, must be removed before. 

 

 

Fasten the pressing screw of the explosion-proof cable gland (Torque see Chapter 3, Technical 
Data). 

 

  Outside the light fitting appropriate measures (e.g. pull relief clips) must be taken to 

protect the connection cable from twist and it must be ensured that no tensile forces react 
on the wiring and the cable entry! 

 

  The diameter of the connection cable must correspond to the sealing range of the 

explosion-proof cable gland (see Chapter 3, Technical Data)! 

 

  Cable entries, which are not used, must be closed with the enclosed closure plug 

(Torque see Chapter 3, Technical Data)! An inlaid dust protective disc, if existing, must 
be removed before. 

 

  The conductors must not be damaged when skinning resp. stripping the cable! 

 

  When stripping the cable special attention needs to be paid to the correct length of the 

conductor end sections (see Chapter 3, Technical Data)! 

 

 

Connect the conductors of the connection cable to the right terminals as per marking. 

 

  It is important to ensure that the bare conductor is fully inserted into the terminal and that 

no cable insulation is clamped! 

 

 

 

 

Modes of operation 

 

Stand-by operation: 
The light fitting switches on automatically in case of a mains failure. 
Only the direct phase (L1) will be connected to connecting point L1 as mains supply monitor. 

 

Maintained operation: 
The light fitting switches on automatically and it may be used as a standard light fitting if mains voltage 
is on. 
The same direct phase (L1) will be connected to connecting point L1 as mains supply monitor and to 
connecting point L1' as switched phase. 

 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 

Summary of Contents for e864 12L Series

Page 1: ...ends on the observance of all safety standards Exact knowledge about all applicable regulations and standards is mandatory for installation maintenance and repair of explosion proof equipment especial...

Page 2: ...ubject to any kind of vibrations it is highly recommended to consult the Adolf Schuch GmbH before starting the installation Every structural modification will cause dangerous situations and consequent...

Page 3: ...up of a series connection which itself is built up of parallel connections of single LEDs Failures of LEDs do not necessarily lead to a change in the power consumption which is recognized by the emerg...

Page 4: ...itions after a correctly performed switching sequence at L1 terminal an operational life test is immediately initiated If the switching sequence is correctly carried out on L1 terminal an operational...

Page 5: ...connection between the emergency light unit and the battery is re established 2 4 LED Signals The two colored LED red green which is integrated in the reflector of the light fitting does show the work...

Page 6: ...the light fitting 3 Technical Data Series e864 12L Capacity of emergency battery Nominal operating time in case of emergency Index of luminous flux Explosion proof LED Emergency Light Fitting for oper...

Page 7: ...ion position in any direction except upwards light output Rated luminous flux ca 16 with e864 12L42 ca 12 with e864 12L60 Spare battery Typ 8020 6 V 1 6 Ah NiCd 1 hour emergency light time standard ve...

Page 8: ...fitting in an explosive dust atmosphere is depending on the properties of the surrounding dust Please ensure that there will be an adequate difference between the maximum surface temperature of the f...

Page 9: ...es which are not used must be closed with the enclosed closure plug Torque see Chapter 3 Technical Data An inlaid dust protective disc if existing must be removed before The conductors must not be dam...

Page 10: ...elivery state there is no electrical connection between the emergency battery and the emergency light unit If no power supply is present even if the light fitting is connected to the emergency battery...

Page 11: ...k and ensure that the light fitting has been installed according to the regulations and in the allowed operating position the explosion proof cable glands resp explosion proof locking screws are secur...

Page 12: ...s in 3 phase circuits and with a common neutral conductor N Light fittings with emergency light unit OK fault If the common neutral conductor is interrupted and voltage is present then light fittings...

Page 13: ...have got thermal insulation characteristic features It is necessary to clean the fitting from dust regularly In case the dust layer may be higher than 5 mm it must be ensured that the surface tempera...

Page 14: ...ctor with mounted LED modules has been described in the separate instructions which can be found attached to the spare parts to be supplied 6 5 Environmental advice This device has got an accumulator...

Page 15: ...L 014124 04 15...

Page 16: ...16 L 01412 4 04 The test certificates are ready to be loaded down from our homepage www schuch de or we shall send it on request Misprints modifications and errors are excepted...

Reviews: