L-01412-4-04 

!

2.5   Instructions for special versions with remote cutoff switch 

 

Special versions of these lighting fixtures are equipped to be connected to a remote cutoff switch. 
Through a remote cutoff switch (isolated switching contact) it is possible to remove the light fitting from 
operation, e.g. during maintenance.  
The remote cutoff switch must be closed during normal operation of the special light fitting. 
If the remote switch is open, there will be no emergency lighting in the case of a power outage. 
A change to the switch position of the remote cutoff switch is only indicated if the fixture is connected 
to a power supply.  

 

  If no power supply is present, when the remote switch is closed (resetting the 

deactivation) the light fitting will not enter emergency lighting mode! 

 

 

 

Functionality and operational life tests that are due to be carried out when the remote cutoff switch is 
deactivated will be postponed until the deactivation is reset, and will be conducted when the necessary 
requirements for the respective test are satisfied. 
The interval of functionality and operational life tests are not affected by deactivating the light fitting. 

 
3.  Technical Data 

 

 

Series: 

 

 

e864. 12L ..  / . / .  

 

 

 

 

 

 

    

│   │  └─ Capacity of emergency battery 

 

 

 

 

 

 

    

│   └─ Nominal operating time in case of emergency 

 

 

 

 

 

 

    

└─ Index of luminous flux 

 

 

 

 

 

 

Explosion-proof LED Emergency Light Fitting for operating in hazardous  

 

 

 

 

 

areas of zones 1 and 21. 

 

 

Explosion protection:  

o

 II 2 G Ex db eb [ib] mb op is q IIC T4 Gb 

 

 

 

 

 

o

 II 2 D Ex op is tb IIIC T80 °C Db 

 

 

Certification: 

 

IBExU 17 ATEX 1026 

 

 

 

 

 

IECEx IBE17.0016 

 

 

Rated voltage: 

 

220…240 V AC; 50...60 Hz 

 

 

 

 

Switching from mains to battery operation at approx. 180 V  

 

 

 

 

 

Switching from battery to mains operation at approx. 195 V 

 

 

Isolation class: 

 

 

 

Ingress protection:  

IP66  (When using an Ex-breathing gland see Section 2) 

 

 

Ambient temperatur: 

-30 °C ... +55 °C  (Standard versions) 

 

 

 

 

 

0 °C ... +45 °C  (Nominal range according to EN 60598-2-22) 

 

 

 

 

 

-30 °C ... 0 °C   (Emergency duration may be limited) 

 

 

 

 

 

Versions for higher ambient temperatures see type plate 

 

 

Power consumption: 

The power consumption of the LED is dependent on production fluctuations 

 

 

 

 

 

as well as on the service temperature. 

 

 

 

 

 

This is why just reference values can be given as follows: 

 

 

 

 

 

e864. 12L42 / . / . : 35 W 

 

 

 

 

 

e864. 12L60 / . / . : 49 W 

 

 

Cable entry: 

 

Cable glands with thread size M25 x 1.5 

 

(if supplied) 

 

Sealing range: 7 - 17 mm (for 10 - 17 mm remove the small sealing ring) 

 

 

 

 

 

Torques: Connection thread 3 Nm; Pressing screw 2 Nm 

 

 

 

 

 

Torque of locking screw: 5 Nm 

 

 

 

 

 

 

See information label on the front page when having special versions! 

 

 

Summary of Contents for e864 12L Series

Page 1: ...ends on the observance of all safety standards Exact knowledge about all applicable regulations and standards is mandatory for installation maintenance and repair of explosion proof equipment especial...

Page 2: ...ubject to any kind of vibrations it is highly recommended to consult the Adolf Schuch GmbH before starting the installation Every structural modification will cause dangerous situations and consequent...

Page 3: ...up of a series connection which itself is built up of parallel connections of single LEDs Failures of LEDs do not necessarily lead to a change in the power consumption which is recognized by the emerg...

Page 4: ...itions after a correctly performed switching sequence at L1 terminal an operational life test is immediately initiated If the switching sequence is correctly carried out on L1 terminal an operational...

Page 5: ...connection between the emergency light unit and the battery is re established 2 4 LED Signals The two colored LED red green which is integrated in the reflector of the light fitting does show the work...

Page 6: ...the light fitting 3 Technical Data Series e864 12L Capacity of emergency battery Nominal operating time in case of emergency Index of luminous flux Explosion proof LED Emergency Light Fitting for oper...

Page 7: ...ion position in any direction except upwards light output Rated luminous flux ca 16 with e864 12L42 ca 12 with e864 12L60 Spare battery Typ 8020 6 V 1 6 Ah NiCd 1 hour emergency light time standard ve...

Page 8: ...fitting in an explosive dust atmosphere is depending on the properties of the surrounding dust Please ensure that there will be an adequate difference between the maximum surface temperature of the f...

Page 9: ...es which are not used must be closed with the enclosed closure plug Torque see Chapter 3 Technical Data An inlaid dust protective disc if existing must be removed before The conductors must not be dam...

Page 10: ...elivery state there is no electrical connection between the emergency battery and the emergency light unit If no power supply is present even if the light fitting is connected to the emergency battery...

Page 11: ...k and ensure that the light fitting has been installed according to the regulations and in the allowed operating position the explosion proof cable glands resp explosion proof locking screws are secur...

Page 12: ...s in 3 phase circuits and with a common neutral conductor N Light fittings with emergency light unit OK fault If the common neutral conductor is interrupted and voltage is present then light fittings...

Page 13: ...have got thermal insulation characteristic features It is necessary to clean the fitting from dust regularly In case the dust layer may be higher than 5 mm it must be ensured that the surface tempera...

Page 14: ...ctor with mounted LED modules has been described in the separate instructions which can be found attached to the spare parts to be supplied 6 5 Environmental advice This device has got an accumulator...

Page 15: ...L 014124 04 15...

Page 16: ...16 L 01412 4 04 The test certificates are ready to be loaded down from our homepage www schuch de or we shall send it on request Misprints modifications and errors are excepted...

Reviews: