47
601
RESET settings
Yes/No
“
YES
”: Resets all user settings including the setting of the discharge time of
the stages (SETUP/401)
and the function “Use switching output FAN as
stage switching output
” (SETUP/406) to factory settings. The function
“First Setup” will be restarted immediately, the control will be stopped and
all AUTO-stages will be switched off according to a switch-off sequence.
FON-stages are excludes and remain to stay active. In case the option
“First Setup” will be cancelled or completed, the control restarts its
operation.
The condition for this behaviour is, that the control is activated
(SETUP/100/PFC = ON or SETUP/310 = ON).
Exception:
The stage database (SETUP/402, 403, 404 und 405) is not
reset.
NOTE:
The nominal voltage, the current transformer factor, the voltage
transformer factor and the phase correction angle must be entered again, to
obtain correct measurement. In order to detect the phase angle, the
automatic initialisation (AI) can be executed as well.
602
RESET stage database
Yes/No
“
YES
”
: Resets the stage database (SETUP/402, 403, 404, 405) to factory
settings.
The option “Switching output fan as further stage output”
(SETUP/406) will not be affected by this function.
EXCEPTION:
The setting of the discharge time of the stages (SETUP/401)
is not reset.
!
CAUTION
All active stages, including the FON stages, are immediately switched off.
NOTE:
All stage sizes, switching cycle counters and operating hour
counters of the stages are reset. In this way, the previously recorded power
loss, switching cycles and operating hours of all stages are lost. An active
service alarm with regard to the switching cycles and operating hours of
stages is thus also reset.
NOTE:
If the stage recognition is switched off (SETUP/308 = NO), the
control is switched off, set to
“OFF” and blocked.
The stage sizes must be entered manually again (SETUP/402). The control
must be switched on again (SETUP/100/PFC or SETUP/310).
The setting
of the control remains blocked until the current transformer factor is entered
once and at least one stage size is entered manually. Then, the control can
be switch on again.
603
RESET operating hour counter
Yes/No
“
YES
”: Resets the operating hour counter of the controller.
After confirming the setting with
“YES”
, the RESET takes place. The setting
will automatically return to
“NO”
.
604
RESET average system power factor (SPF)
Yes/No
“
YES
”: Resets the average system power factor (SPF). After confirming the
setting with
“YES”
, the RESET takes place. The setting will automatically
return to
“NO”
.
605
RESET maximum measured temperature
Yes/No
“
YES
”: Resets the value of the maximum measured temperature. After
confirming the setting with
“YES”
, the RESET takes place. The setting will
automatically return to
“NO”
.
606
RESET alarm messages
Yes/No