46
stages have been switched off, the control stops for as long as one out of
these three alarms is still active.
520
THD-U / THD-I / TEMP 2 alarm = switch off active stages
Yes/No
“
NO
”: active stages are not switched off in case of an alarm.
“
YES
”: If the digital input alarm is triggered after running out of the delay
time of 10 s, all active stages (
“AUTO” & “FON”) are switched off one by one
referring to the switch-off interval set under SETUP/523 and are locked for
30 min. The last active stage is switched off first, when the switch-off interval
has run out after the signalling of the alarm. Then, the other stages are
switched off one by one referring to the switch-off interval. As all active
stages have been switched off, the control stops for as long as one out of
these three alarms is still active.
NOTE:
The control is stopped while the alarm is still active. The stages
which have been switched off by the alarm system are locked for max. 30
min. Active
“FON” stages are also switched off and blocked. Stages which
have been switched on manually are NOT switched off. If stages are
switched off manually, they are only locked until the discharge time is
expired.
NOTE:
The THD-U-, THD-I- or the Temp2-alarm can also lock the control
system and initiate the sequential deactivation of active stages.
521
I-Low-Alarm
Yes/No
“
YES
”: I-LOW-alarm is enabled.
In case of a measuring current of <5 mA, the notifications
“I Lo” and Alarm
appear on the display after a delay time of 60 s. The contact of the alarm
relay will be opened.
If the measuring current is equal to 5 mA or succeeds this value again and
option
“Manual Reset” (SETUP/501=No) is deactivated, all alarm
notifications will be reset automatically after a delay time of 15 s.
NOTE:
The alarm relay will only be reset if there is no further alarm pending
at the same time.
“
NO
”: The I-LOW-Alarm is permanently deactivated and will not be
signalized.
NOTE:
The digital input function (suppression of I-Low) will only work if the
I-LOW-Alarm is enabled (SETUP/518=I Lo).
522
Delay time I-High-Alarm
NOTE:
Delay time can only be configured in integer values. The time value
can be set until an I-High-Alarm occurs.
NOTE:
Is the alarm no longer active, the alarm messages (display and alarm
relay) is reset automatically after a delay time of 15 s.
523
THD-U-, THD-I-, TEMP2- , digital input alarm/ switch-off interval of stages 1...255 s
Adjustable stage switch-off interval in case of an alarm, in consideration of
activation of SETUP/503 for THD-U-, THD-I-, TEMP2-alarm) and of
SETUP/520 for digital input alarm.
600
RESET
MENU
Enables resetting of all user settings, the values saved by the controller and the counters. In addition, it
is possible to display the software version of the device and to change the password (PIN) of the expert
setup menu.
600 RESET menu