25
TROUBLESHOOTING
S
TART
-
UP PROBLEMS
Moving an already-configured MCU from one cabinet to another one of a different type, could lead to the following screen.
Also, by selecting the correct type of new cabinet, it will not be possible to start the application correctly and the screen will be
shown again.
Given that the MCU on USMPW and CBC100x system, or CONNECTIVITY PANEL already possesses a configuration based on a
type of cabinet, it cannot start.
Proceed as follows to resolve this situation:
•
Temporarily select the old cabinet type (this will be incompatible with the current cabinet). The application is now able to
start-up, but of course various errors will be displayed.
•
Change the MCU or CONNECTIVITY PANEL configuration by removing all the PM and all configured batteries.
•
Save the “empty” configuration.
•
Restart the MCU or CONNECTIVITY PANEL.
Upon the subsequent start-up the MCU or CONNECTIVITY PANEL will be able to recognise the new type of cabinet and prepare
itself to receive the correct configuration.