11
Power Cabinet A, selected for display and/or changes to the configuration if required. The check mark
highlights the presence in the cabinet of at least one configured Power Module.
Power Cabinet A, configured as not present in the system and not selected.
Power Module configured as present in the system.
Power Module configured as not present in the system.
External temperature probe (connected to the ASB): enabled
External temperature probe (connected to the ASB): disabled
Note: In the case of a PWC 300 being configured with 7 PM’s, at least one of them shall be set as redundant,
otherwise the tag number indicating the PM number will turn red and a warning will appear when saving the
configuration.
C
OMBO
C
ABINET CONFIGURATION
If Combo Cabinet is selected, the current configuration of the combo cabinet is displayed in the righthand side. If at least one Power
Module or one Battery Unit Array is inserted a check mark on the symbol of the Combo Cabinet will be present, confirming its
presence in the system. If all Power Modules and Battery Unit Arrays are removed, the corresponding Combo Cabinet is also
removed from the system; the Combo Cabinet you are operating from cannot be excluded from the configuration.
CBC 130
CBC 100X