ONVENTIONAL BATTERY CONNECTION AND CONFIGURATION
There are 3 possible connection types:
•
Shared: with a single battery connection shared by all the UPS Cabinets within the system.
•
Separate: each UPS Cabinet is connected exclusively to one or more Battery Cabinets electrically separated from the
Battery Cabinets connected to the other UPS Cabinets.
•
Groups/Pairs: the UPS Cabinets are grouped into pairs. Each pair has a separate battery source.
NOTES
- The only configuration possible with a single UPS Cabinet is the connection to shared batteries.
- The Pair connection is only permitted where there are 4 UPS Cabinets.
- Following a configuration modification, if the conditions to maintain the selection made are not present, the system
will automatically reset the configuration to shared batteries, issuing a suitable warning message.
S
HARED BATTERIES
By touching the text box it is possible to configure the battery capacity (Ah).
Representation of a configuration to shared batteries with only 2 UPS Cabinets.