24
N
OMINAL FREQUENCY CHANGE
Once the output frequency is selected, to activate the change, perform the following operations:
- Open the locking switch on all PM.
- Wait for a few seconds to allow all PM to completely shut down.
- Restart the system following the start-up procedure (for details refer to the “USMPW user manual” or “USMPX user manual”).
A
DVANCED SYSTEM SETTINGS
This page allows the configuration of the autostart, the automatic shut down and the low battery warning time.
A
UTO RESTART
If during battery operation the system switches off due to the end of autonomy, a remote shutdown command or due to a self-
shutdown, when the power is restored the system automatically switches on if the function is enabled; however, it remains in stand-
by if the function is disabled [Default → Function ENABLED]
Note: it is not possible to adjust the autorestart delay (set at 15 seconds).
A
UTO POWER OFF
If, during battery operation, the percentage of the load powered by the system falls below the 5% threshold (load switched off or
disconnected), after 40 seconds the system automatically switches off if the function is enabled; the system continues to function
normally via battery if the function is disabled [Default → Function DISABLED].
B
ATTERY LOW TIME
Set the estimated runtime (expressed in minutes between 0 and 105), below which the system displays the battery low alarm
[Default → 3].