SD-I-U-...
12 / 28
Montage- und Anschlussanleitung / UNIVERSAL-Gateway für serielle Diagnose
Mounting and wiring instructions / UNIVERSAL gateway for serial diagnostics
Instructions de montage et de câblage / Passerelle UNIVERSEL pour diagnostic série
english
Technical data
Power supply:
24 VDC –15 % / +20 % (stabilised PELV)
Recommended fuse:
external fuse 1 A slow-blow
Current consumption at 24 VDC:
max. 500 mA, internally protected
Operating temperature:
0 – 55 °C, in case of vertical mounting position
Storage temperature:
– 25 °C … + 70 °C
Ambient conditions:
humidity 30 % … 85 %, no condensation
Protection class:
IP20
Mounting location:
earthed lockable control cabinet with at least IP54 protection class
Resistance to vibrations:
if fitted between two lateral clamping blocks on the rail
to IEC 60068-2-6
10 … 57 Hz / 0,35 mm and 57 … 150 Hz / 5 g
Resistance to shocks:
to IEC 60068-2-29
10 g
Electromagnetic immunity:
to EN 61000-4-2 (ESD)
± 6 kV contact discharge / ± 8 kV air discharge
to EN 61000-4-3 (HF field)
10 V/m / 80 % AM
to EN 61000-4-4 (Burst)
± 1 kV all connections
to EN 61000-4-5 (Surge)
± 1 kV all connections
to EN 61000-4-6 (HF cables)
10 V all connections
Electromagnetic interfering radiation:
to EN 61000-6-4 (2002)
Interfering radiation industrial environments
Rated insulation voltage U
i
:
32 V
Rated impulse withstand voltage U
imp
:
0,5 kV
Overvoltage category:
II
Degree of pollution:
2
Dimensions (width/height/depth):
50 x 100 x 80 mm (= mounting height starting from rail)
Time to readiness delay after switch-on:
6 s
Fieldbus interface
Refer to the description of the fieldbus module as of page 19
Wiring example
Sensor
X1 (IN)
X1 (IN)
X1 (IN)
Y1 (OUT)
Y1 (OUT)
Y1 (OUT)
X2 (IN)
X2 (IN)
X2 (IN)
Y2 (OUT)
Y2 (OUT)
Y2 (OUT)
SD-OUT
SD-OUT
SD-OUT
SD-IN
SD-IN
SD-IN
SD-Interface
SD-I-DP-VO-2
PROFIBUS DP
SPS/PLC
Sensor
Sensor
Auswertung
Sicherheits-
Gateway
PROFIBUS-
Safety monito-
ring module /
Safety circuit
UNIVERSAL
gateway
FIELDBUS