background image

   

 

 

 

 

 

 

 

 

 

Smoke extraction damper ERK-SO

 

 

 

 

TECHNICAL DOCUMENTATION

 

          Models 

and 

dimensions 

 

 

 

Construction subject to change 

 

 

No 

return 

possible 

      Version: 

2017-11-28 

Page 

Use 

 

The smoke extraction damper type ERK-SO can be fitted as 
shown in the following table. 

1)

  when installed next to each other 

2)

  when installed on top of each other 

3)  

in connection with mounting brackets WE-S and on- 

site suspensions and horizontal damper blade axle 

 

Table 3 - Usability 

 

 
 
 

General information 

o

 

During mounting or installation, there is a risk of in-
juries. To avoid injuries, personal protective equip-
ment (PPE) must be worn. 

o

 

Smoke extraction dampers must be installed such 
that external forces do not impair their functioning. 
During mounting it may be required to provide rein-
forcements for the housing or the like. The require-
ment of statically load-bearing lintels may have to be 
taken into consideration.  

o

 

Improper transport/handling may result in dam-
age/functional impairment. In addition to that, the 
film of the transport packaging must be removed 
and the delivery inspected for completeness. 

o

 

In storage, smoke extraction dampers must be pro-
tected from dust, dirt, moisture and the effects of 
extreme temperatures. They must not be exposed to 
direct effects of the weather. 

 
 
 
 
 

4)

  in connection with ceiling frame DR-S 

5)

  in connection with on-site suspensions 

6)

   in connection with on-site fastening frames and suspen-

sions 

 
 
 
 
 
 
 
 

o

 

The smoke extraction dampers must be protected 
from dirt and damage. After installation is complete, 
any dirt must be removed immediately. 

o

 

Enough space must be provided for installation, mor-
tar lining, etc.  

o

 

Carry out a functional check of the smoke extraction 
damper before and after mounting and ensure ready 
access.  

o

 

Electrical installations or work on electrical compo-
nents may only be carried out by skilled electricians. 
The supply voltage must be switched off when per-
forming this work. 

o

 

Always check whether the housing needs to be ex-
tended on the b side (MS) for the corresponding in-
stallation situations (e.g. the thickness of the sup-
porting structure and a possible connection to the 
smoke extraction duct must be considered). 

 

 

Use 

Instal-

lation 

Material/Model 

Mini-
mum 

thickness 

[

mm

]

 

Minimum distance 

of two ERK-SO 

from one another 

[

mm

]

 

Fire resistance 

class 

For no-

tes, see 

page 

WALL

 

solid 

Apparent 

density 

 450 kg/m³ 

in 

for example, concrete, masonry ac-
cording to EN 1996 or DIN 1053; solid 
plaster wall boards according to EN 
12859 or DIN 18163 

100 

0 (4)

1) 

 

200

2) 

EI 90(v

ew

,i

o)S 

1000 C

10000

 MA multi 

on

3) 

for example, concrete, masonry ac-
cording to EN 1996 or DIN 1053; solid 
plaster wall boards according to EN 
12859 or DIN 18163 

100 200 

EI 90(v

ew

,i

o)S 

1000 C

10000

 MA multi 

14 

CEILING 

solid 

Apparent 

density 

 650±200  

kg/m³ 

in

3)

 

for example, concrete, aerated con-
crete 

150 200 

EI 90(h

ow

,i

o)S 

1000 C

10000

 MA multi 

17 

to

4) 

for example, concrete, aerated con-
crete 

150 200 

EI 90(h

ow

,i

o)S 

1000 C

10000

 MA multi 

20 

SMOKE EXT

R

ACTI

ON 

DUCT

horizontal 

Apparent 

density 

 520 kg/m³ 

in

5) 

in accordance with EN 12101-7, 
tested according to EN 1366-8 

35 200 

EI 90(v

ed

,i

o)S 

1000 C

10000

 MA multi 

21 

on

5) 

in accordance with EN 12101-7, 
tested according to EN 1366-8 

35 200 

EI 90(v

ed

,i

o)S 

1000 C

10000

 MA multi 

21 

to

6) 

in accordance with EN 12101-7, 
tested according to EN 1366-8 

35 200 

EI 90(v

ed

,i

o)S 

1000 C

10000

 MA multi 

22 

Summary of Contents for ERK-SO

Page 1: ...ng the necessary sup ply air within the smoke extraction installa tion For use in solid walls ceilings and smoke ex traction lines For automatic AA or manual MA triggering SPECIAL FEATURES Thermally i...

Page 2: ...smoke extraction ducts 21 Connection options on or in horizontal smoke extraction ducts 21 Connection options on horizontal smoke extraction ducts in accordance with EN 12101 7 tested according to EN...

Page 3: ...meframe 60 s or torque monitor ing For use in solid walls and ceilings for supplying air or ventilat ing smoke also in combination with smoke extraction lines in compliance with EN 121017 which have b...

Page 4: ...1 ERK SO housing consisting of 2 x 25 mm silicate structural panels 2 Profile connection frame PAR optional 3 Damper blade consisting of 3 x 20 mm silicate structural panels 4 Stop bar 40 x 20 mm with...

Page 5: ...amper blade the lengths L standard are assigned to the heights H On request larger L dimensions are also possible Length L mm Other B or H dimensions 1 mm steps are available at an ex tra charge furth...

Page 6: ...he inspection of the actuator by loosening the hexagon screws M6 x 100 mm H L a BS b MS 200 H 400 530 65 75 401 H 565 630 65 175 566 H 634 630 50 190 635 H 711 700 85 255 712 H 800 800 135 275 Detail...

Page 7: ...t be provided for installation mor tar lining etc o Carry out a functional check of the smoke extraction damper before and after mounting and ensure ready access o Electrical installations or work on...

Page 8: ...ay not be less than 100 mm When performing a mortar lining or direct installation make sure that the housing is not pressed toward the inside reinforcement If neces sary a statically active lintel mus...

Page 9: ...des Gap 10 60 mm the dimensions of the threaded rods and the U steel can be found on pages 24 27 Suspension Detail B Mineral wool A1 melting point 1000 C gap 15 5 mm In the lower gap place only in cas...

Page 10: ...additional accessory package is required for the connection to the smoke extraction dampers as a function of the dimension vertical position of the damper blade axle independent of the actuator positi...

Page 11: ...ously MG II to III according to DIN 1053 or fire pro tection mortar of suit able grades Gap 10 60 mm U steel B vertical axle 1500 Mortar of category M2 5 to M15 according to EN 998 2 previously MG II...

Page 12: ...I I II II II II III III III III III III III 225 I I I I I I I I I I I I I II II II II III III III III III III III 250 I I I I I I I I I I I I I II II II II III III III III III III III 275 I I I I I I...

Page 13: ...I I I I II II II II II II II II II II II 325 I I I I I I I I I I I I I II II II II II II II II II II II 350 I I I I I I I I I I I I I II II II II II II II II II II II 375 I I I I I I I I I I I I I II...

Page 14: ...le only o The distance to load bearing adjacent components wall solid ceiling is due to the construction at least 100 mm o Additional suspension required with U steel pole brace Wall opening Housing l...

Page 15: ...f Insulfrax paper 50 x 5 mm thick Number and arrangement of mounting brackets WE S Proposed installation ERK SO in front of the concrete wall with suspension The brackets are fastened to the reinforce...

Page 16: ...M8 M8 M8 M8 M8 M8 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M12 M12 M12 M12 M12 M12 M12 500 M8 M8 M8 M8 M8 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M12 M12 M12 M12 M12 M12 M12 M14 550 M8 M8 M8 M10 M1...

Page 17: ...en by the mortar manufac turer must be observed If the smoke extraction damper is installed during the construction of the ceiling the gaps s can be omitted The mortar bed depth must be executed in th...

Page 18: ...0 mm Wet installation Mortar gap 10 60 mm Mortar of category M2 5 to M15 in ac cordance with EN 998 2 previously MG II to III according to DIN 1053 or fire protection mortar of suitable grades Mortar...

Page 19: ...pax concrete Figure 12 Arrangement of WE S when installed in solid ceilings 200 225 250 275 300 325 350 375 400 450 500 550 600 650 700 750 800 900 1000 1100 1200 1300 1400 1500 200 2 2 2 2 2 2 2 2 2...

Page 20: ...be at least 200 mm o The distance to load bearing adjacent components wall is due to the construction at least 100 mm Mounting information o Adjust connection between ERK SO and ceiling with water gla...

Page 21: ...zontal smoke extraction duct 8 Smoke extraction ducts to EN 12101 7 tested to EN 1366 8 Min damper Optionally smoke extraction duct or finishing protective grating ASG E Smoke extraction duct to EN 12...

Page 22: ...reinforcement in the smoke extraction duct The arrangement depends on the size of the ERK SO and the smoke extraction duct Detail B Detail A Circumferential fastening frame on site for connecting the...

Page 23: ...g abP ETA etc Smoke extraction duct made of silicate struc tural panel in accordance with EN 12101 7 tested accord ing to EN 1366 8 Smoke extraction duct made of sheet steel in accordance with EN 121...

Page 24: ...A 04 0026 for suspending the smoke extraction dampers M8 to M12 M16 and M20 Group of 2 Group of 4 Core bore diam eter is always 6 mm It is recommended to secure threaded rods screwed into the screw so...

Page 25: ...er threaded rod N KP M6 0 18 20 1 120 6 12 29 M8 0 32 36 6 219 6 22 38 M10 0 50 58 0 348 0 35 47 M12 0 73 84 3 505 8 51 55 M14 0 97 115 0 690 0 70 33 M16 1 35 157 0 942 0 96 02 M20 2 08 245 0 1470 0 1...

Page 26: ...ction Certified to EN 1366 1 Figure 20 Covered suspending brackets M12 Figure 21 Dimensions of the suspension covering Table 12 Suspension coverings Please note The weights of the suspension covering...

Page 27: ...ng as shown opposite must be mounted Example of dimensioning Given ERK SO with the dimensions W 800 mm H 400 mm Suspension height 4 m The following weights must be added ERK SO according to table on p...

Page 28: ...e in suspended ceilings shaft walls connected ventilation ducts etc if necessary They must be built in sufficient numbers and size and must not im pair the functioning of the smoke extraction dampers...

Page 29: ...gram Correction table for octave weighting dB Oct fm Hz 63 125 250 500 1000 2000 4000 8000 KFO dB 4 2 0 1 4 9 15 21 Sound power per octave LW LWA KFO fm Hz 63 125 250 500 1000 2000 4000 8000 LW dB 37...

Page 30: ...0 405 0 450 0 540 0 585 0 630 0 675 FQK 500 0 059 0 078 0 098 0 117 0 137 0 156 0 176 0 195 0 215 0 234 0 254 0 273 0 293 0 332 0 371 0 449 0 488 0 527 0 566 FQmin 0 701 0 610 0 542 0 475 0 429 0 418...

Page 31: ...EK14 EK12 SPMa 1SR EK20 BE24 24 V AC DC EK21 BE230 230 V AC o Communication devices for actuator EK12 EK14 e g SPMa1SR part of EK14 or SPLM 4S 0SD Mod o Profile connection frame type PAR o Security gr...

Page 32: ...VDE guidelines Technical data Table 14 Technical data of actuators Actuator type EK10 SEL 1 90 EK11 SEL 2 90 EK12 SEL 1 90 SLC EK14 EK12 SPMa 1SR Rated voltage V AC DC 24 AC 230 In connection with SP...

Page 33: ...ction diagram for actuator type EK12 SEL 1 90 SLC 24 V AC DC EK14 EK12 SPMa 1SR 2 wire technology 2 strand see safety communication modules power line system SLC type SPMa 1SR or SPLM 4S 0SD Mod Cover...

Page 34: ...side MS ASG2 or on both sides ASG3 o delivered loose 1 piece ASG4 2 pieces ASG5 Figure 26 Security grille type ASG E Recommendation Mounting of the ASG E in connection with the PAR with W or H 700 mm...

Page 35: ...velocity relative to Astirn V m h l s Volumetric flow LWA dB A A weighted sound power level LW dB Sound power level octave LW LWA KFO B mm Width H mm Height L mm Length FQmin m Smallest flow cross se...

Page 36: ...ernal impregnation 07 ACTUATOR EK10 SEL 1 90 24 V AC DC STANDARD ACTUATOR EK11 SEL 2 90 230 V AC EK12 SEL 1 90 SLC 24 V AC DC additional communication de vice required please order separately EK14 EK1...

Page 37: ...EK10 24 V AC DC will be delivered Moreover the standard length will be assigned to the height H Alternative models or accessories at an extra charge Select as desired Housing and damper blade with ad...

Page 38: ...ts made of steel 2 pieces are required for ERK SO The ceiling frame DR S is pressed circumferentially against ERK SO and solid ceiling and screwed to the ceiling If it is necessary due to the size the...

Page 39: ...according to DIN 31051 and EN 13306 o For and after commissioning the function of the entire smoke extraction system interaction of all compo nents must be regularly checked and documented in writing...

Page 40: ...No Declaration of perfor mance no Series Actuator The following functional steps have been carried out according to the documents installation mounting and operating instructions before commissioning...

Page 41: ...nfo schako de Web www schako de SAMPLE Functional test protocol for smoke extraction dampers Cons No ____________________ Defects found during the test on ________________________________________ Slug...

Page 42: ...L 2343 Luxembourg A 1060 Wien PL 05 500 Piaseczno Phone 352 403 157 1 Phone 352 403 157 1 Phone 43 1 890 24 62 Phone 48 22 7263570 Fax 352 403 157 66 Fax 352 403 157 66 Fax 43 1 890 24 62 50 Fax 48 22...

Page 43: ...to M12 24 Figure 20 Suspension fastenings M16 and M20 24 Figure 21 Covered suspending brackets M12 26 Figure 22 Dimensions of the suspension covering 26 Figure 23 Covered suspending brackets M14 to M...

Reviews:

Related manuals for ERK-SO