S.B.C. Elettronica S.p.A. - Engineering Division
HPDxxN – High Power User’s Manual
31
b41.1
At speed
.
With b40.7=0 if the speed difference between motor and reference is lower than
Pr14 and higher than Pr15, b41.1 will be 1, otherwise it will be 0. With b40.7=1, if motor
speed is lower than Pr14 and higher than Pr15, b41.1 will be 1, otherwise it will be 0.
b41.2
Zero speed
.
If motor speed (Pr0) is zero rpm, b41.2=1, otherwise b41.2=0.
b41.3
Forward
.
If motor speed (Pr0) is positive b41.3=1, otherwise b41.3=0.
b41.4
Drive Healthy
.
If =1 no alarms are present, otherwise =0.
b41.5
Hardware enable status
.
1 when hardware enable is set
.
b41.6
Temperature pre-alarm
.
10 degrees before reaching the maximum temperature of the
power stage, b41.6 is set to 1.
b41.7
External alarm
.
Alarm for user’s equipment.
b41.8
Auxiliary alarm
.
Second alarm for user’s equipment.
b41.9
Calibration failed
.
b41.9=1 indicates that initial calibration of current offsets has terminated
incorrectly.
b41.10 Speed control saturation
.
b41.10=1 when the speed control loop is delivering maximum
current.
b41.11 I2T active
.
Indicates that Pr36 has reached 100.0 % and therefore the drive is restricting
current to the rated value.
b41.12 Drive enabled
.
b41.13 Keypad fault
.
b41.12=1 if communication between keypad and drive has failed.
b41.14 External operating mode.
If set to 1 an external operating mode is installed.
b41.15 External operating mode time slot.
If set to 1 indicates that the external operating mode
is controlled at 2 ms intervals otherwise at 512
µ
s.
b42.0
Selector to configure encoder emulation.
b42.1
Selector to configure encoder emulation.
b42.2
Selector to configure encoder emulation.
Pr32 up to 9000 rpm
================
Pr32 up to 3500 rpm
==========================
Pr32 up to 875 rpm
=====================================
ENCODER OUT
16384 8192 4096 2048
1024
512 256 128
b42.0
0 1 0 1 0 1 0 1
b42.1
0 0 1 1 0 0 1 1
b42.2
0 0 0 0 1 1 1 1
the double line indicates encoder resolutions available in the various speed ranges
Default value is 1024
b42.4
24V over current.
Digital output trip.
b42.5
Frequency input
(board X6). If set to 1 the frequency input is programmed to receive two
phases in quadrature. This is the default. If set to 0 it is enabled to receive a
frequency/direction type input.
b42.6
Torque compensation
.
Default=1. When set to 1 torque compensation is implemented to
improve linearity of response.
b99.6
Extended menu enable
.
Default=0. Set to 1 to enable the extended menu.
b99.7
Security
.
Default=0. Set to 1 to prevent parameter modification.
b99.13 pico-PLC status.
Default=1. If on 1 the PLC program is run, if on zero the program is not
run and the PLC instructions can be modified if required.